Heavy foundry dust branch

A foundry extraction branch handles heavy particulate at 2,000 CFM.

Inputs

Branch airflow & duct
CFM
in

Live results

Round duct and settling limit

Round duct and settling limitDUCT SPEED4,527FPMMINIMUM SPEED5,000FPMVEL. PRESSURE1.278in.wgSPEED MARGIN-9.459%Round sectionLongitudinal flowØ 9 inSettling risk at invertMinimum transport speedDuct speed4,527 FPMMin 5,000 FPM
The round inlet represents the entered diameter. Amber particles along the invert indicate an entered speed below the selected minimum.

Settling risk: actual speed is below the selected minimum.

Duct speed
4,527.07 FPM
Minimum speed
5,000 FPM
Vel. pressure
1.2777 in.wg
Speed margin
-9.45852 %

Round duct sizing

Actual branch airflow
2,000 CFM
Duct cross-section
0.441786 ft²
Inside diameter
9 in
Band minimum diameter
7.81764 in
Band maximum diameter
8.5638 in
Upper screening speed
6,000 FPM

Worked calculation at the starting values

The heavy-class minimum is 5,000 FPM. A diameter suitable for lighter material can leave heavy dust below its transport target.

  1. Cross-section = π × 0.2286² ÷ 4 = 0.04104331 m².
  2. Actual speed = 0.9438949 ÷ 0.04104331 = 22.99754 m/s.
  3. Velocity pressure = (4,527.074 ÷ 4005)² = 1.277704 in.wg.
Starting result snapshot
Duct speed
4,527.07 FPM
Minimum speed
5,000 FPM
Vel. pressure
1.2777 in.wg
Speed margin
-9.45852 %

Equations and assumptions

Transport speed

V = Q ÷ (π × D² ÷ 4)

Use the actual branch airflow and the inside duct diameter. The selected minima are 2,000, 3,500, 4,000 and 5,000 FPM. Check the actual transport class with the ACGIH design manual and confirm it on site.

Velocity pressure

VP = (V_FPM ÷ 4005)²

The coefficient is for standard-density air and yields in.wg. SI pressure converts that result to Pa. For nonstandard air, correct by the actual-to-standard density ratio. VP is dynamic pressure.

Diameter band

D = √(4 × Q ÷ (π × V))

The upper diameter corresponds to the minimum speed. The lower diameter uses a selected upper screening speed of 3,000, 4,000, 4,500 or 6,000 FPM. Final diameter also depends on erosion, abrasion, noise and fan pressure.

References

More worked examples