Low-solids fume branch

A low-solids exhaust branch carries 620 CFM through a round 7-inch duct.

Inputs

Branch airflow & duct
CFM
in

Live results

Round duct and settling limit

Round duct and settling limitDUCT SPEED2,320FPMMINIMUM SPEED2,000FPMVEL. PRESSURE0.3355in.wgSPEED MARGIN+15.99%Round sectionLongitudinal flowØ 7 inParticles in transportMinimum transport speedDuct speed2,320 FPMMin 2,000 FPM
The round inlet represents the entered diameter. Amber particles along the invert indicate an entered speed below the selected minimum.

Actual speed falls within the selected diameter screening band.

Duct speed
2,319.89 FPM
Minimum speed
2,000 FPM
Vel. pressure
0.33553 in.wg
Speed margin
+15.9947 %

Round duct sizing

Actual branch airflow
620 CFM
Duct cross-section
0.267254 ft²
Inside diameter
7 in
Band minimum diameter
6.15562 in
Band maximum diameter
7.53906 in
Upper screening speed
3,000 FPM

Worked calculation at the starting values

This uses the gases and fumes screening class. Evaluate contaminant-specific velocity requirements separately.

  1. Cross-section = π × 0.1778² ÷ 4 = 0.02482867 m².
  2. Actual speed = 0.2926074 ÷ 0.02482867 = 11.78506 m/s.
  3. Velocity pressure = (2,319.894 ÷ 4005)² = 0.33553 in.wg.
Starting result snapshot
Duct speed
2,319.89 FPM
Minimum speed
2,000 FPM
Vel. pressure
0.33553 in.wg
Speed margin
+15.9947 %

Equations and assumptions

Transport speed

V = Q ÷ (π × D² ÷ 4)

Use the actual branch airflow and the inside duct diameter. The selected minima are 2,000, 3,500, 4,000 and 5,000 FPM. Check the actual transport class with the ACGIH design manual and confirm it on site.

Velocity pressure

VP = (V_FPM ÷ 4005)²

The coefficient is for standard-density air and yields in.wg. SI pressure converts that result to Pa. For nonstandard air, correct by the actual-to-standard density ratio. VP is dynamic pressure.

Diameter band

D = √(4 × Q ÷ (π × V))

The upper diameter corresponds to the minimum speed. The lower diameter uses a selected upper screening speed of 3,000, 4,000, 4,500 or 6,000 FPM. Final diameter also depends on erosion, abrasion, noise and fan pressure.

References

More worked examples

Open calculator defaults