Metal grinding pickup branch

A metal grinding pickup uses a 200 mm branch at 2,650 m³/h.

Inputs

Branch airflow & duct
m³/h
mm

Live results

Round duct and settling limit

Round duct and settling limitDUCT SPEED23.43m/sMINIMUM SPEED20.32m/sVEL. PRESSURE330.4PaSPEED MARGIN+15.31%Round sectionLongitudinal flowØ 200 mmParticles in transportMinimum transport speedDuct speed23.43 m/sMin 20.32 m/s
The round inlet represents the entered diameter. Amber particles along the invert indicate an entered speed below the selected minimum.

Actual speed is above the screening band. Review erosion, noise and fan pressure.

Duct speed
23.4311 m/s
Minimum speed
20.32 m/s
Vel. pressure
330.376 Pa
Speed margin
+15.3107 %

Round duct sizing

Actual branch airflow
2,650 m³/h
Duct cross-section
0.0314159 m²
Inside diameter
200 mm
Band minimum diameter
202.483 mm
Band maximum diameter
214.766 mm
Upper screening speed
22.86 m/s

Worked calculation at the starting values

Compare velocity pressure with the high end of the screening band, then balance noise, erosion and fan energy.

  1. Cross-section = π × 0.2² ÷ 4 = 0.03141593 m².
  2. Actual speed = 0.7361111 ÷ 0.03141593 = 23.43114 m/s.
  3. Velocity pressure = (4,612.43 ÷ 4005)² = 1.326339 in.wg.
Starting result snapshot
Duct speed
23.4311 m/s
Minimum speed
20.32 m/s
Vel. pressure
330.376 Pa
Speed margin
+15.3107 %

Equations and assumptions

Transport speed

V = Q ÷ (π × D² ÷ 4)

Use the actual branch airflow and the inside duct diameter. The selected minima are 2,000, 3,500, 4,000 and 5,000 FPM. Check the actual transport class with the ACGIH design manual and confirm it on site.

Velocity pressure

VP = (V_FPM ÷ 4005)²

The coefficient is for standard-density air and yields in.wg. SI pressure converts that result to Pa. For nonstandard air, correct by the actual-to-standard density ratio. VP is dynamic pressure.

Diameter band

D = √(4 × Q ÷ (π × V))

The upper diameter corresponds to the minimum speed. The lower diameter uses a selected upper screening speed of 3,000, 4,000, 4,500 or 6,000 FPM. Final diameter also depends on erosion, abrasion, noise and fan pressure.

References

More worked examples

Open calculator defaults