Use the actual branch airflow and the inside duct diameter. The selected minima are 2,000, 3,500, 4,000 and 5,000 FPM. Check the actual transport class with the ACGIH design manual and confirm it on site.
Velocity pressure
VP = (V_FPM ÷ 4005)²
The coefficient is for standard-density air and yields in.wg. SI pressure converts that result to Pa. For nonstandard air, correct by the actual-to-standard density ratio. VP is dynamic pressure.
Diameter band
D = √(4 × Q ÷ (π × V))
The upper diameter corresponds to the minimum speed. The lower diameter uses a selected upper screening speed of 3,000, 4,000, 4,500 or 6,000 FPM. Final diameter also depends on erosion, abrasion, noise and fan pressure.
CleanroomVentLab · Calculation sheet · US customary
Oversized wood branch
Inputs
Branch airflow
1,400 CFM
Inside round diameter
12 in
Transport class
Dry wood / plastics
Results
Duct speed
1,782.54 FPM
Minimum speed
3,500 FPM
Vel. pressure
0.198094 in.wg
Speed margin
-49.0704 %
Actual branch airflow
1,400 CFM
Duct cross-section
0.785398 ft²
Inside diameter
12 in
Band minimum diameter
8.0107 in
Band maximum diameter
8.5638 in
Upper screening speed
4,000 FPM
Settling risk: actual speed is below the selected minimum.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.