Presets use the midpoint of the UC Davis CO₂-rate ranges in mL/(kg·h), interpolated with temperature. The metric heat basis is one tonne. The US readout uses a 2,000 lb short ton. Custom mode uses rate = reference rate × Q₁₀^[(T − Tref)/10].
Use T in °C and RH as a fraction. The model treats the produce surface as saturated at room temperature.
Weight loss & coil selection
m(t) = m₀ × exp[−k × VPD × days / 100]
Apple, early potato, and lettuce coefficients use ASHRAE tabulated reference values or close commodity proxies. The strawberry and broccoli coefficients are illustrative. The TD bands reflect high-humidity starting points. Confirm coil, airflow, control, and packaging effects with the supplier.
Does higher humidity change the respiration heat result?
The preset respiration model responds to temperature. Humidity drives the modeled moisture loss through vapor pressure deficit. Actual measured respiration can also vary by cultivar, maturity, and atmosphere.
Why does the potato preset start at 5 °C?
That is the lowest point in the early-crop potato respiration data used here. The VPD model still works at lower temperatures. Choose commodity- and end-use-specific guidance for actual storage.
ColdChainLab · Engineering calculation
Produce Respiration Heat & Transpiration Calculator
Metric SI · https://calcsheetlab.com/coldchainlab/produce-respiration-weight-loss/
Inputs
Commodity
Golden Delicious apples
Stored product mass
10500 kg
Storage temperature
5 °C
Storage relative humidity
92 %
Storage duration
30 days
Effective moisture-loss coefficient
0.50112 %/(kPa·day)
Results
Resp. heat
372.2W
Vapor deficit
0.07kPa
Weight loss
1.04%
Coil TD band
3.9–5K
Respiration heat per stored ton
35.4W/t
Respiration rate
6mL CO₂/(kg·h)
Initial moisture loss per day
0.035%
Moisture mass lost
109.6kg
Estimated remaining mass
10,390.4kg
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.