Commodity storage

Produce Respiration Heat & Transpiration Calculator

Estimate produce respiration heat, vapor pressure deficit, transpiration weight loss, and a preliminary evaporator TD band.

Resp. heat
372.2W
Vapor deficit
0.07kPa
Weight loss
1.04%
Coil TD band
3.9–5K
Edit inputs

Inputs

Edit any value to recalculate.

Commodity & storage

Use a weight-loss coefficient for the packaging, maturity, and airflow of the lot.

kg
°C
%
days
%/(kPa·day)

Respiration heat by storage temperature

Respiration heat by storage temperatureThe marker shows the selected temperature on the commodity curve when published points bracket it.Respiration / W per tonneStorage temperature / °C0510152005099149Respiration curveOperating point

The marker shows the selected temperature on the commodity curve when published points bracket it.

Calculation breakdown

Respiration heat per stored ton
35.4W/t
Respiration rate
6mL CO₂/(kg·h)
Initial moisture loss per day
0.035%
Moisture mass lost
109.6kg
Estimated remaining mass
10,390.4kg

Worked examples

Open a case with its assumptions loaded, then edit the inputs.

Formulas and assumptions

Respiration heat

q (W/t) = respiration rate × 122 × 4,184 / 86,400

Presets use the midpoint of the UC Davis CO₂-rate ranges in mL/(kg·h), interpolated with temperature. The metric heat basis is one tonne. The US readout uses a 2,000 lb short ton. Custom mode uses rate = reference rate × Q₁₀^[(T − Tref)/10].

Vapor pressure deficit

VPD = 0.6108 × exp[17.27T / (T + 237.3)] × (1 − RH)

Use T in °C and RH as a fraction. The model treats the produce surface as saturated at room temperature.

Weight loss & coil selection

m(t) = m₀ × exp[−k × VPD × days / 100]

Apple, early potato, and lettuce coefficients use ASHRAE tabulated reference values or close commodity proxies. The strawberry and broccoli coefficients are illustrative. The TD bands reflect high-humidity starting points. Confirm coil, airflow, control, and packaging effects with the supplier.

References

Questions and answers

Does higher humidity change the respiration heat result?

The preset respiration model responds to temperature. Humidity drives the modeled moisture loss through vapor pressure deficit. Actual measured respiration can also vary by cultivar, maturity, and atmosphere.

Why does the potato preset start at 5 °C?

That is the lowest point in the early-crop potato respiration data used here. The VPD model still works at lower temperatures. Choose commodity- and end-use-specific guidance for actual storage.