Methodology

The calculators use explicit geometry and photometric assumptions for engineering screening. For final design, check the adopted code, fixture photometry, and measured or simulated point grids.

Units and rounding

Inputs are stored in SI. One foot is exactly 0.3048 m. A footcandle is 1 lumen per square foot. A foot-lambert is 1/π candela per square foot. US and SI report the same unrounded calculation. The egress checks use the exact conversions of the stated footcandle limits.

Lumen Method Calculator

Calculate the room cavity ratio from the room, workplane, and fixture heights. Use the utilization factor at that RCR and surface reflectance. Pair absolute luminaire lumens with room utilization (utilance). Pair relative lamp lumens with published CU and ballast factor.

Verify point illuminance, glare and uniformity with fixture photometry. The manufacturer’s spacing criterion is a layout screen.

IES glossary · zonal cavity interreflectance and room geometry ↗

Point-by-Point Illuminance

Read candela at the computed nadir and azimuth from the luminaire file. For the second position, use its own directional candela.

This direct-light screen omits reflections, obstructions and finite luminaire size. Sum projections onto the actual wall normal for a fixed receiving plane.

IES RP-8-22 · calculation geometry, section 3.3 ↗

Lighting Power Density

Presets use the I-P ASHRAE 90.1-2019 Table 9.6.1 base allowances. Select Custom for an adopted IECC or other project-specific allowance.

Classifications, exemptions, additional allowances and mandatory controls require project review. Enter control savings as an annual energy assumption.

ASHRAE Handbook · 90.1-2019 Table 9.6.1 values, I-P edition ↗

Daylight Factor Calculator

This simplified split-flux screen uses 1 − Ravg. The published BRE average daylight factor equation uses 1 − Ravg².

Use climate-based daylight modeling for certification and a luminance-based analysis for glare. High reflectance can amplify this estimate.

BRE Research Report 296306 · average daylight factor, section 2.1 ↗

Lumens, Candela & Beam Angle

In the uniform-cone approximation the axial intensity equals the average intensity inside the cone. Real FWHM beam distributions need an IES or LDT file.

Use measured photometry for beam edges, off-axis illuminance and non-Lambertian materials.

IES glossary · luminous intensity ↗

Roadway Pole Spacing

Select a maintained illuminance target for the road or parking class. Apply the street-side utilization and light loss to the flux in one repeating roadway cell.

The supplied spacing / height limit is a project heuristic. Verify RP-8 pavement uniformity, glare, luminance, and classification using grid photometry.

IES · RP-8 roadway and parking facilities ↗

LED String & Junction Temperature

Use the data-sheet forward voltage at rated current, including bin tolerances where known. Select the heat sink arrangement that matches the luminaire.

Check current sharing, driver minimum output voltage and start-up behavior, LED bin variation, and actual assembly thermal resistance.

Cree LED · thermal resistance and forward-voltage temperature coefficient ↗

Emergency Egress Lighting

Use floor-level readings along the egress route. Enter measured 90-minute values where available, or apply the same end-of-discharge factor to each initial reading.

Confirm the locally adopted edition, listed emergency equipment, inrush and battery discharge curves. Field-test the full required emergency duration.

NFPA · NFPA 101 Life Safety Code, section 7.9 ↗