Construct exact Modbus RTU FC03 Read Holding Register requests
Function Code 0x03 (Read Holding Registers) is the workhorse command for polling VFDs, smart power meters, solar inverters and industrial PLCs over RS-485. Each request is exactly 8 bytes: 1-byte Slave ID, 1-byte Function 0x03, 2-byte big-endian start register, 2-byte big-endian register count, and 2-byte little-endian CRC-16.
Verify your wire bytes before sending them from a USB-RS485 dongle or firmware state machine, and inspect the required t3.5 silent framing gap for your bus baud rate.
Formulas
FC03 PDU = [ID, 0x03, Addr_Hi, Addr_Lo, Qty_Hi, Qty_Lo]CRC-16/MODBUS(01 03 00 00 00 0A) = 0xCDC5 → wire C5 CDAir time at 9600 bps = 8 bytes × 11 bits ÷ 9600 = 9.17 ms
Worked example
Polling 10 holding registers from address 0 on Slave ID 1 produces the 8-byte RTU frame `01 03 00 00 00 0A C5 CD` with t3.5 = 4,010 µs at 9,600 bps.