AC feeder voltage drop & cable withstand calculator

Calculate three-phase feeder voltage drop from conductor R + jX and check IEC-style adiabatic cable withstand at an entered fault clearing time.

Inputs

Conductor & raceway
Steady load
Cable thermal duty
Use 0 to show withstand only.

Feeder impedance and cable withstand

60 Hz · US customaryEdit inputs
Feeder impedance and cable withstand at 60 Hz AC DROP8.77VDROP PCT1.827%LOAD VOLTS471.23VTHERMAL LIMIT34.28kAThree-phase feederSourceLoadL1L2L3One-way 375 ft1 × setsR + jX per phase8.77 V dropAdiabatic clearing curveWithstand (kA)0.01 s5 sDrop budget1.83% drop3% budget

Detailed results
Longitudinal voltage drop
8.77 V
Longitudinal drop percent
1.827%
Phasor receiving line voltage
471.23 V
Phasor magnitude voltage drop
8.77 V
AC resistance per conductor
0.0628 Ω/kft
Reactance per conductor
0.0332 Ω/kft
Equivalent one-way resistance
0.02355 Ω
Equivalent one-way reactance
0.01247 Ω
Conductor cross-section
107.22 mm²
Adiabatic conductor coefficient
143 A√s/mm²
Withstand per conductor
34.28 kA
Withstand across parallel sets
34.28 kA
Allowable I²t per conductor
235,081,271 A²s
Modeled fault I²t per conductor
39,200,000 A²s
Adiabatic limit used
16.68%

Formulas & assumptions

Three-phase longitudinal drop

ΔV = √3 · I · L · (R · cos φ + X · sin φ) / n

Use a one-way length with matching R/X units and divide by the number of identical parallel sets. The longitudinal expression is the common steady-load approximation. The magnitude result retains the quadrature term and solves for receiving voltage.

Resistance and reactance

R₇₅ ≈ 1000 · ρ₇₅ · F_AC / A, X ≈ 2πf · 0.0002 · ln(2.6/0.7788) · F_raceway

Estimated Ω/km uses round conductors, ρ₇₅ of 0.02097 (Cu) or 0.0347 (Al) Ω·mm²/m, F_AC = 1 + min(0.18, A/3000) · g, with g = 1.5 for steel or 1 for PVC. The reactance multiplier is 1.2 for steel and 1 for PVC. Enter manufacturer AC R/X at operating temperature and frequency when available.

Short-circuit thermal withstand

I²t ≤ (k · A)², I_max = k · A / √t

A is the area of one conductor in mm². k depends on insulation, metal and the permitted temperature rise. Total withstand assumes equal current in all sets. The PVC coefficient changes above 300 mm².

Balanced three-phase lagging load. The effective R/X model omits installation-specific spacing and heating. The 0.01–5 s adiabatic screen requires conductor and termination checks. For current-limiting devices, use published let-through I²t and verify coordination.