THD-I and true RMS
THD = √Σ(I_h², h > 1) / I₁, I_RMS = √ΣI_h²
Percent-mode entries use the fundamental as their reference. The spectrum covers odd orders through 13. The frequency of a component is its order times 50 Hz or 60 Hz.
Calculate THD-I, true RMS current, distortion power factor, triplen current in a Wye neutral, and an RMS-normalized transformer K-factor.
| Order | Frequency | RMS current | % of I₁ |
|---|---|---|---|
| h1 | 60 Hz | 100 A | 100% |
| h3 | 180 Hz | 28 A | 28% |
| h5 | 300 Hz | 18 A | 18% |
| h7 | 420 Hz | 12 A | 12% |
| h9 | 540 Hz | 7 A | 7% |
| h11 | 660 Hz | 5 A | 5% |
| h13 | 780 Hz | 3 A | 3% |
THD = √Σ(I_h², h > 1) / I₁, I_RMS = √ΣI_h²
Percent-mode entries use the fundamental as their reference. The spectrum covers odd orders through 13. The frequency of a component is its order times 50 Hz or 60 Hz.
PF_true = PF_displacement / √(1 + THD²)
Use THD as a decimal. This relationship assumes sinusoidal voltage, so real power comes from the fundamental voltage and current.
I_N = 3 · √(I₃² + I₉²), K = Σ[(I_h/I_RMS)² · h²]
Third and ninth harmonics add arithmetically across balanced four-wire Wye phases at each order. Different orders combine by RMS. The K-factor uses total RMS as the base and the harmonic winding eddy-current weighting associated with IEEE C57.110.
I_max/I_rated ≈ √[(1 + e)/(1 + K · e)]
e is rated winding eddy-current loss divided by rated winding DC I²R loss. This holds the winding loss constant for the entered spectrum and excludes other stray losses and cooling constraints.
Equal phase spectra with balanced sequence and sinusoidal voltage. The displayed THD-I describes the entered current spectrum. IEEE 519 limits are assessed at the point of common coupling with the applicable quantities, including TDD. Transformer thermal loading also depends on construction and rated current.