600 V motor with measured inrush

A 200 hp motor on a 600 V board has a measured starting ratio of 6.8 kVA/hp.

Inputs

Motor nameplate
Use 0 for the code range midpoint, or the lower bound for open-ended Code V.
Starter & bus
Centrifugal duty

Starting voltage dip and cubic power

60 Hz · US customaryEdit inputs
Starting voltage dip and cubic power at 60 Hz FULL LOAD171.54ALOCKED ROTOR1.309KAVOLTAGE DIP7.25%ENERGY SAVED355.9KkWhBus voltage during startingNominal bus600 VEstimated during start556.48 VStarting demand1.36K kVACentrifugal affinity curve100% power0% speed100% speedVoltage dip7.25%8% budget

Detailed results
Mechanical shaft rating
149.14 kW
Baseline electrical power
158.66 kW
Estimated full-load line current
171.54 A
Inrush ratio used
6.8 kVA/hp
Nominal DOL locked-rotor current
1,308.66 A
Code band lower current
1,212.44 A
Code band upper current (exclusive)
1,366.4 A
Selected starting current
1,308.66 A
Starting apparent power
1,360 kVA
Bus short-circuit capacity
17.39 MVA
Bus voltage dip
7.25%
Reduced-speed electrical power
87.48 kW
Baseline energy per year
793,297.74 kWh
Reduced-speed energy per year
437,398.99 kWh
Annual energy savings
355,898.75 kWh
Annual energy cost savings
42,707.85 CAD/yr

Worked calculation

Use the measured ratio instead of the code midpoint. At 200 hp, 6.8 kVA/hp gives 1,360 starting kVA. Use this value with the transformer fault level.

Starting apparent power
1,360 kVA
Bus short-circuit capacity
17.39 MVA
Bus voltage dip
7.25%

Values in this solution use the original example inputs.

Formulas & assumptions

Nameplate and inrush

I_FLA = 1000 · kW_shaft / (√3 · V_LL · η · PF), SKVA_DOL = hp · (kVA/hp)

Use operating-frequency nameplate data. Bounded NEMA codes use the midpoint of their interval. Code V has no upper bound. The measured inrush ratio can supersede the estimate.

Starter and source dip

Dip (%) = 100 · SKVA / (SKVA + 1000 · MVA_sc)

DOL uses the full code estimate. Wye-Delta uses one-third of DOL line current for a Delta-running motor. Soft starter and VFD inputs set modeled current in multiples of FLA. For the transformer-only source, MVA_sc = transformer kVA / (1000 · %Z/100).

Centrifugal affinity law

P₂ = P₁ · (N₂/N₁)³, ΔkWh = (P₁ − P₂) · annual hours

Assumes the same operating hours, friction-dominated duty and unchanged efficiency, with drive losses excluded. Run this part for variable-torque pumps and fans with minimal static head.

Use actual nameplate current and starting curves for equipment sizing. The impedance-divider dip is a screening estimate without cable impedance, source X/R or Wye-Delta transition transients.