- Mechanical shaft rating
- 149.14 kW
- Baseline electrical power
- 158.66 kW
- Estimated full-load line current
- 171.54 A
- Inrush ratio used
- 6.8 kVA/hp
- Nominal DOL locked-rotor current
- 1,308.66 A
- Code band lower current
- 1,212.44 A
- Code band upper current (exclusive)
- 1,366.4 A
- Selected starting current
- 1,308.66 A
- Starting apparent power
- 1,360 kVA
- Bus short-circuit capacity
- 17.39 MVA
- Bus voltage dip
- 7.25%
- Reduced-speed electrical power
- 87.48 kW
- Baseline energy per year
- 793,297.74 kWh
- Reduced-speed energy per year
- 437,398.99 kWh
- Annual energy savings
- 355,898.75 kWh
- Annual energy cost savings