ASCE/SEI 7-16 §§26.9–26.13, 27.3, 30.3

Wind velocity & MWFRS pressures

Calculate qz and roof-height qh, then resolve wall and roof pressures for both signs of internal pressure.

Calculation sheet
Export

Inputs

Wind and exposure
mph
ft
ft

Use eave height for roof slopes of 10° or less.

Building envelope
ft
ft
°
Wind factors, opening and C&C
Velocity and pressure factors
ft
ft²

0 retains the unreduced −1.3 coefficient.

Low-rise components and cladding
VELOCITY qz
27.202psf
ROOF qh
28.654psf
EXPOSURE Kz
0.945
ROOF MIN.
-21.882psf

Building pressure sectionWindwardLeewardGCₚᵢ ±0.18h 32 ftExposure with heightHeight zExposure C36.8 ft001.13Kz exposure factor15 ft floor
Wall pressure directions and the exposure profile. Arrow lengths reflect the active wind pressure cases.

Calculation detail

Ground elevation Kₑ
1
Roof exposure Kₕ
0.996
Positive internal qᵢ
28.654 psf
Internal coefficient |GCₚᵢ|
0.18
Leeward Cₚ
-0.39
Aspect L/B
1.548
Directional surface pressures
SurfaceCₚExternal (psf)+GCₚᵢ (psf)−GCₚᵢ (psf)
Windward wall0.818.497713.3423.6553
Leeward wall-0.3903-9.5065-14.6642-4.3489
Sidewall-0.7-17.0489-22.2065-11.8912
Windward roof-0.6867-16.7241-21.8818-11.5665
Windward roof / alt.-0.132-3.2149-8.37261.9427
Leeward roof-0.42-10.2293-15.387-5.0717

How the calculation works

Velocity pressure changes with height

Kz = 2.01(z/zg)^(2/α) in the exposure layer. The evaluation height has a 15 ft floor and a ceiling at the gradient height. The worksheet evaluates the original mph/ft equation qz = 0.00256 Kz Kzt Kd Ke V². Ke = exp(−0.0000362 zₑ), with zₑ in feet.

Surface coefficients and pressure signs

The Chapter 27 directional procedure uses local qz at the windward wall and qh at the leeward and side walls and roof. Leeward wall Cₚ is interpolated using L/B. Roof strips follow distance downwind for low slope or parallel wind, and gable slopes use h/L and slope interpolation normal to the ridge.

Keep internal cases paired

Net pressure is external qGCₚ minus internal qᵢGCₚᵢ. Windward dominant opening height can set positive qᵢ for a partially enclosed building. Negative internal pressure uses qh. A positive surface result acts toward the face. Apply a consistent internal-pressure sign to the building for a load case.

Calculate low-rise C&C pressure for a selected zone

Choose the zone and both external GCₚ values from the applicable Chapter 30 figure for the roof geometry and effective wind area. Eq. 30.3-1 uses qh for both terms and includes the adverse internal sign for each direction. The reported design magnitude is at least 16 psf inward and outward. The external coefficient already includes gust effect.

Design scope

Directional MWFRS screening for rectangular flat or gable buildings. Check governing load cases and minimums separately. The optional C&C check uses the supplied low-rise zone coefficients. Chapter 28 envelope cases, open-roof net coefficients, torsional load cases and overhangs use distinct provisions.