Worked example · ASCE/SEI 7-16 §§12.8.6–12.8.7, Table 12.12-1

Single-story steel workshop

A workshop uses the general drift limit for its cladding and partitions. The exception is available only for finishes detailed for the expected motion.

Calculation sheet
Export

Inputs

Drift limits
ft
in
Story actions
kip
kip

Use 1 as the ASCE default. The capacity-first convention is inverted for the code check.

Importance factor override
Importance override

Enter 0 to use the risk category.

STORY DRIFT
3.24in
DRIFT RATIO
1.5%
STABILITY θ
0.0314
DRIFT CHECK
Within limit
No P-Delta amplification

θ is at or below 0.10 and within the maximum stability coefficient.

Drift: Within limit

The comparison includes the amplified drift when the simplified P-Delta multiplier applies.

Deflected story frameElastic / design displacementδₓₑ 0.72 inΔ 3.24 inStability thresholdsStability coefficientθ = 0.031400.25Amplification threshold0.10Stability limit θmax0.1111P-Delta multiplier1
Elastic and amplified deformations are exaggerated for comparison. The gauge identifies both code thresholds.

Calculation detail

Risk or override Iₑ
1
Elastic drift δₓₑ
0.72 in
Allowable ratio
2%
Allowable displacement
4.32 in
Code ratio β (demand/capacity)
1
Maximum stability θmax
0.1111
Stability check
No amplification
P-Delta multiplier
1
Drift after P-Delta
3.24 in

How the calculation works

Read this example

Compare the general screening row with the single-story exception after checking which wall and ceiling assemblies can move.

Preset result: STORY DRIFT 3.24 in.

Convert the analysis drift

Design story drift Δ = Cᴅδₓₑ/Iₑ. Divide by the story height in consistent units and compare against the specified screening row of Table 12.12-1. Most masonry shear walls use 0.007, and masonry cantilever shear walls use 0.010.

Evaluate stability before applying amplification

θ = PₓΔIₑ/(VₓhₛₓCᴅ) and θmax = min(0.5/(βCᴅ), 0.25). Above θmax, the story is potentially unstable. Within the maximum, θ greater than 0.10 requires explicit second-order analysis or the permitted 1/(1 − θ) amplification.

Check the qualifications for drift exceptions

The ≤4-story row assumes the relevant interior and exterior assemblies accommodate drift. The single-story exception also requires detailed drift accommodation. Building separation and the special requirement for certain moment frames in seismic categories D–F are separate checks.

Design scope

Use drifts and forces from the applicable seismic analysis in the same direction. Check building separation, moment-frame rules, and drift compatibility in addition to this worksheet.

Source references
  • ASCE/SEI 7-16 standardhttps://ascelibrary.org/doi/book/10.1061/9780784414248
  • FEMA P-749 seismic design conceptshttps://www.fema.gov/sites/default/files/documents/fema_p-749-earthquake-resistant-design-concepts_112022.pdf
  • FEMA P-1051 design exampleshttps://www.fema.gov/sites/default/files/2020-07/fema_nehrp-seismic-provisions-examples_p-1051_20160701.pdf

More story drift & p-delta examples