Atmospheric steam at 0 psig
A vented kettle runs at the standard atmosphere. Use zero gauge pressure to read the boiling point and latent heat.
Inputs
Inputs
- Steam pressure
- 0 psig
- Steam condition
- Dry saturated
Calculation results
- Atmospheric reference uses 1.01325 bar absolute.
- Saturation temperature
- 211.95°F
- Saturated liquid enthalpy h_f
- 180.13Btu/lb
- Latent heat h_fg
- 970.14Btu/lb
- Saturated vapor enthalpy h_g
- 1,150.27Btu/lb
- State enthalpy h
- 1,150.27Btu/lb
- Saturated vapor volume v_g
- 26.80362ft³/lb
- Saturated vapor density
- 0.0373lb/ft³
- State specific volume v
- 26.80362ft³/lb
- State density ρ
- 0.0373lb/ft³
- Saturated liquid entropy s_f
- 0.3121Btu/(lb·°R)
- Saturated vapor entropy s_g
- 1.7566Btu/(lb·°R)
- State entropy s
- 1.7566Btu/(lb·°R)
- Absolute pressure
- 14.7psia
- State temperature
- 211.95°F
- Phase
- Dry saturated
Calculation basis
- Gauge to absolute
P_abs = P_g + 1.01325 bar - Saturation and superheat
T_sat = IF97 R4(P_abs); h_fg = h_g − h_f - Wet steam
h = h_f + x·h_fg; s = s_f + x·(s_g − s_f); v = v_f + x·(v_g − v_f)
Check the original case
Read saturation temperature and absolute pressure together. Raising gauge pressure moves the working point along the saturation curve.
- Saturation temperature211.95 °F
- Saturated vapor enthalpy h_g1,150.27 Btu/lb
- State specific volume v26.80362 ft³/lb
- State density ρ0.0373 lb/ft³
Formulas and assumptions
Gauge to absolute
P_abs = P_g + 1.01325 bar
The reference atmosphere is 14.69595 psia. The input range is 0–600 psig, equivalent to 0–41.36854 bar g.
Saturation and superheat
T_sat = IF97 R4(P_abs); h_fg = h_g − h_f
Regions 1 and 2 supply the saturated liquid and vapor at T_sat. Region 2 also evaluates superheated states directly up to 600 °C.
Wet steam
h = h_f + x·h_fg; s = s_f + x·(s_g − s_f); v = v_f + x·(v_g − v_f)
Dryness is the mass fraction of vapor. The equilibrium mixture density is 1/v.
Worked examples
Open a case to edit its inputs.