CleanroomVentLab · Calculation sheet · Metric SI
ISO 5 aseptic filling zone
Inputs
- Length
- 6 m
- Width
- 3 m
- Clear height
- 2.7 m
- ISO class
- ISO Class 5
- Airflow basis
- Unidirectional velocity
- Unidirectional velocity
- 0.36 m/s
- FFU nominal module
- 600 × 1,200 mm
- Rated flow per FFU
- 1,150 m³/h
Results
- Supply flow
- 23,328 m³/h
- Air changes
- 480 h⁻¹
- FFU count
- 21 units
- Coverage
- 84 %
- Floor area
- 18 m²
- Room volume
- 48.6 m³
- Installed FFU capacity
- 24,150 m³/h
- Capacity above target
- 822 m³/h
- 100:1 ideal recovery
- 0.575646 min
- Installed FFU face area
- 15.12 m²
- Uniform grid capacity
- 25 units
Particle concentrations (particles/m³)
| Threshold | Formula | ISO table limit |
|---|---|---|
| ≥ 0.1 µm | 100,000 | 100,000 |
| ≥ 0.2 µm | 23,651.44 | 23,700 |
| ≥ 0.3 µm | 10,176.25 | 10,200 |
| ≥ 0.5 µm | 3,516.757 | 3,520 |
| ≥ 1 µm | 831.7638 | 832 |
| ≥ 5 µm | 29.25111 | Unassigned |
Counts are cumulative. Use the published classification value for each applicable class and particle size.
The required FFU count fits the uniform grid before service clearances.
For preliminary engineering and EHS / Industrial Hygiene review. Design calculations do not replace review by a licensed professional engineer (PE) and a certified industrial hygienist (CIH), commissioning tests, ISO 14644 classification or certification, or assessment against the applicable NFPA 86 edition.