ISO 5 aseptic filling zone

A work zone over a filling line uses downward flow and 600 × 1,200 mm nominal modules.

Inputs

Room geometry
m
m
m
Supply & ceiling
m/s
m³/h
Use the rated flow at the planned operating pressure.

Live results

Ceiling grid and particle curve

Ceiling grid and particle curveSUPPLY FLOW23,330m³/hAIR CHANGES480h⁻¹FFU COUNT21unitsCOVERAGE84%FFU ceiling gridDownflow supplyISO 5 · particles/m³110⁴10⁸0.10.20.30.515µmUniform ceiling fitFFU count21 neededGrid 25 units
Filled ceiling cells represent the share covered by FFUs. Hollow circles on the particle curve mark formula-only values.

The required FFU count fits the uniform grid before service clearances.

Supply flow
23,328 m³/h
Air changes
480 h⁻¹
FFU count
21 units
Coverage
84 %

Room and airflow

Floor area
18 m²
Room volume
48.6 m³
Installed FFU capacity
24,150 m³/h
Capacity above target
822 m³/h
100:1 ideal recovery
0.575646 min

Ceiling layout

Installed FFU face area
15.12 m²
Uniform grid capacity
25 units

Particle concentrations (particles/m³)

ThresholdFormulaISO table limit
≥ 0.1 µm100,000100,000
≥ 0.2 µm23,651.4423,700
≥ 0.3 µm10,176.2510,200
≥ 0.5 µm3,516.7573,520
≥ 1 µm831.7638832
≥ 5 µm29.25111Unassigned

Counts are cumulative. Use the published classification value for each applicable class and particle size.

Worked calculation at the starting values

The formula column includes a 5 µm estimate. The ISO Class 5 classification table leaves that size unassigned.

  1. Room volume = 6 × 3 × 2.7 = 48.6 m³.
  2. Supply = 18 × 0.36 = 6.48 m³/s.
  3. FFU count = round up (6.48 ÷ 0.3194444) = 21 units.
Starting result snapshot
Supply flow
23,328 m³/h
Air changes
480 h⁻¹
FFU count
21 units
Coverage
84 %

Equations and assumptions

Particle concentration

Cₙ = 10ᴺ × (0.1 ÷ D)²·⁰⁸

D is the threshold particle size in µm. Each value includes particles at or above D and is reported in particles/m³. Formula values are shown for all six sizes. Use the separate ISO 14644-1:2015 Table 1 column when a class/size limit is published.

Supply airflow

Q = A × H × ACH ÷ 3600 or Q = A × v

Use SI dimensions (m and m²), v in m/s and Q in m³/s. The unidirectional case assumes flow over the full floor plan. The selected ISO class sets particle criteria independently of the airflow target.

FFU count and ceiling fit

n = ceil(Q ÷ Q_FFU) · coverage = n × A_FFU ÷ A × 100%

Grid capacity uses the better of two uniform module orientations. Lights, sprinklers, service clearance and mixed-orientation layouts need a separate ceiling plan.

100:1 recovery

t₁₀₀ = 60 × ln(100) ÷ ACH

This minute estimate assumes perfect mixing, no continuing source and contaminant-free supply. Measure recovery when applicable under ISO 14644-3. For unidirectional flow it remains a mixed-air benchmark.

References

More worked examples

Open calculator defaults