Leaky pass-through

A pass-through downstream of the clean zone adds a larger parallel leakage path at the first barrier.

Inputs

Pressure setpoints
Pa
Pa
Pa
Pa
A–B leakage paths
m
mm
mm²
B–C leakage paths
m
mm
mm²
Air properties
0.60–0.65 is a common sharp-edge starting range.
kg/m³

Live results

Three-zone pressure ladder

Three-zone pressure ladderA–B STEP+17PaB–C STEP+17PaZONE A OFFSET+289.9m³/hZONE C OFFSET-148.5m³/hClosed-door pressure and room offsetsZone A+34 Pa+289.9 m³/hZone B+17 Pa-141.4 m³/hZone C0 Pa-148.5 m³/hLowest aligned pressure stepPressure+17 PaMin 15 Pa
Arrows follow the calculated pressure gradient. Positive offsets call for more supply and negative offsets call for more exhaust.

Both pressure steps meet the entered magnitude and direction.

A–B step
+17 Pa
B–C step
+17 Pa
Zone A offset
+289.89 m³/h
Zone C offset
-148.509 m³/h

Transfer at each barrier

A → B transfer
+289.89 m³/h
B → C transfer
+148.509 m³/h
A–B equivalent leakage
24,400 mm²
B–C equivalent leakage
12,500 mm²

Room offsets and ladder

Zone A supply minus exhaust
+289.89 m³/h
Zone B supply minus exhaust
-141.381 m³/h
Zone C supply minus exhaust
-148.509 m³/h
Weakest aligned step
+17 Pa
Required step
15 Pa

Worked calculation at the starting values

The differential can meet the target while the required upstream offset rises because the effective leakage area is larger.

  1. A–B equivalent leak area = 7.2 × 0.002 + 0.01 = 0.0244 m².
  2. A–B transfer magnitude = 0.62 × 0.0244 × √(2 × 17 ÷ 1.2) = 0.08052493 m³/s.
  3. Zone B offset = 0.04125253 − (0.08052493) = -0.0392724 m³/s.
Starting result snapshot
A–B step
+17 Pa
B–C step
+17 Pa
Zone A offset
+289.89 m³/h
Zone C offset
-148.509 m³/h

Equations and assumptions

Door-crack and other paths

A = perimeter × gap + A_other

Include only the portion of perimeter with a leak path. Enter wall, pass-through and fitting leakage as equivalent area at the same discharge coefficient.

Signed transfer flow

Qᵢⱼ = sgn(Pᵢ − Pⱼ) × C_d × A × √(2 × |Pᵢ − Pⱼ| ÷ ρ)

Use Pa, m² and kg/m³ for Q in m³/s. All three pressures share the same reference. The differential across each closed barrier determines both rate and direction.

Supply minus exhaust

A: Q_AB · B: Q_BC − Q_AB · C: −Q_BC

These are the room offsets attributable to the two modeled door links. Add other envelope paths and use a balanced airflow network for the full system. Open doors, transients and alarm tolerances require testing.

Ladder check

Minimum aligned step = min(s × ΔP_AB, s × ΔP_BC)

The sign s is +1 for an A-to-C cascade and −1 for containment toward A. The FDA closed-door aseptic guidance gives 10–15 Pa as a typical example between different clean classifications. Use the project pressure specification.

References