Reversed airlock step

An elevated airlock setpoint pushes air into Zone A even though the intended path runs from A toward C.

Inputs

Pressure setpoints
Pa
Pa
Pa
Pa
A–B leakage paths
m
mm
mm²
B–C leakage paths
m
mm
mm²
Air properties
0.60–0.65 is a common sharp-edge starting range.
kg/m³

Live results

Three-zone pressure ladder

Three-zone pressure ladderA–B STEP-8PaB–C STEP+18PaZONE A OFFSET-106m³/hZONE C OFFSET-152.8m³/hClosed-door pressure and room offsetsZone A+10 Pa-106 m³/hZone B+18 Pa+258.8 m³/hZone C0 Pa-152.8 m³/hLowest aligned pressure stepPressure-8 PaMin 10 Pa
Arrows follow the calculated pressure gradient. Positive offsets call for more supply and negative offsets call for more exhaust.

A pressure step reverses the intended flow.

A–B step
-8 Pa
B–C step
+18 Pa
Zone A offset
-105.951 m³/h
Zone C offset
-152.815 m³/h

Transfer at each barrier

A → B transfer
-105.951 m³/h
B → C transfer
+152.815 m³/h
A–B equivalent leakage
13,000 mm²
B–C equivalent leakage
12,500 mm²

Room offsets and ladder

Zone A supply minus exhaust
-105.951 m³/h
Zone B supply minus exhaust
+258.766 m³/h
Zone C supply minus exhaust
-152.815 m³/h
Weakest aligned step
-8 Pa
Required step
10 Pa

Worked calculation at the starting values

Inspect the reversed A–B arrow and the signed Zone A offset. The ladder fails using the selected direction.

  1. A–B equivalent leak area = 6 × 0.002 + 0.001 = 0.013 m².
  2. A–B transfer magnitude = 0.62 × 0.013 × √(2 × 8 ÷ 1.2) = 0.02943096 m³/s.
  3. Zone B offset = 0.0424485 − (-0.02943096) = 0.07187946 m³/s.
Starting result snapshot
A–B step
-8 Pa
B–C step
+18 Pa
Zone A offset
-105.951 m³/h
Zone C offset
-152.815 m³/h

Equations and assumptions

Door-crack and other paths

A = perimeter × gap + A_other

Include only the portion of perimeter with a leak path. Enter wall, pass-through and fitting leakage as equivalent area at the same discharge coefficient.

Signed transfer flow

Qᵢⱼ = sgn(Pᵢ − Pⱼ) × C_d × A × √(2 × |Pᵢ − Pⱼ| ÷ ρ)

Use Pa, m² and kg/m³ for Q in m³/s. All three pressures share the same reference. The differential across each closed barrier determines both rate and direction.

Supply minus exhaust

A: Q_AB · B: Q_BC − Q_AB · C: −Q_BC

These are the room offsets attributable to the two modeled door links. Add other envelope paths and use a balanced airflow network for the full system. Open doors, transients and alarm tolerances require testing.

Ladder check

Minimum aligned step = min(s × ΔP_AB, s × ΔP_BC)

The sign s is +1 for an A-to-C cascade and −1 for containment toward A. The FDA closed-door aseptic guidance gives 10–15 Pa as a typical example between different clean classifications. Use the project pressure specification.

References

More worked examples

Open calculator defaults