Quiet vapor pickup

A plain face sits near a low-energy vapor release with little assumed crossdraft.

Inputs

Hood geometry
ft²
ft
Velocity & duct
FPM
in
Use −1 for the default by hood edge.

Live results

Capture contours and exhaust path

Capture contours and exhaust pathEXHAUST FLOW107.5CFMSOURCE SPEED50FPMFACE SPEED86FPMSTATIC DRAW0.07479in.wgSource and capture fieldExhaust ductX = 0.3 ftSource distance screenDistance X0.3 ftGuide 1.5 × Ø
The source marker moves with capture distance. Cerulean paths show air entering the hood and continuing into the exhaust duct.

Verify capture at the release point under operating crossdrafts.

Exhaust flow
107.5 CFM
Source speed
50 FPM
Face speed
86 FPM
Static draw
0.0747884 in.wg

Duct and entrance

Duct velocity
788.39 FPM
Duct velocity pressure
0.0387505 in.wg
Entry loss coefficient
0.93
Irrecoverable entry loss
0.0360379 in.wg
Hood static suction magnitude
0.0747884 in.wg

Worked calculation at the starting values

The 50 FPM preset applies at the source. Compare it with the higher calculated velocity at the hood face.

  1. Reach area = 10 × 0.09144² + 0.1161288 in m².
  2. Required flow = 0.05073435 m³/s at 0.254 m/s capture velocity with the entered hood geometry.
  3. Static suction = (1 + 0.93) × 9.652315 = 18.62897 Pa.
Starting result snapshot
Exhaust flow
107.5 CFM
Source speed
50 FPM
Face speed
86 FPM
Static draw
0.0747884 in.wg

Equations and assumptions

Freestanding face

Q = k × V_c × (10 × X² + A)

DallaValle approximation with k = 1 for plain hoods and k = 0.75 for flanged hoods. Use ft, ft² and FPM for CFM, or m, m² and m/s for m³/s. The result is sensitive to the square of X.

Long slot

Q = V_c × max(A, k × 3.7 × L × X)

L is slot length. The line-sink relation suits a long, narrow opening. The model uses face area as a lower bound at very short distances. Compare A/L to the capture distance and use a slot-specific design for nonuniform slots.

Face and duct velocity

V_face = Q ÷ A · V_duct = Q ÷ (π × D² ÷ 4)

The target is measured at the source. The face and duct values answer different questions. Presets between 50 and 2,000 FPM are starting points for different source energies and crossdrafts.

Entry and static suction

VP = (FPM ÷ 4005)² · |SPₕ| = (1 + Fₕ) × VP

VP is in in.wg at standard air density. Irrecoverable entry loss equals Fₕ × VP. Static suction is shown as a magnitude. Auto Fₕ uses example coefficients 0.93 for plain and 0.49 for flanged openings.

References

More worked examples

Open calculator defaults