Remote sanding source

A sanding source is relatively far from a plain freestanding hood.

Inputs

Hood geometry
ft²
ft
Velocity & duct
FPM
in
Use −1 for the default by hood edge.

Live results

Capture contours and exhaust path

Capture contours and exhaust pathEXHAUST FLOW16,910CFMSOURCE SPEED500FPMFACE SPEED5,285FPMSTATIC DRAW22.85in.wgSource and capture fieldExhaust ductX = 1.75 ftSource distance screenDistance X1.75 ftGuide 1.5 × Ø
The source marker moves with capture distance. Cerulean paths show air entering the hood and continuing into the exhaust duct.

Verify capture at the release point under operating crossdrafts.

Exhaust flow
16,912.5 CFM
Source speed
500 FPM
Face speed
5,285.16 FPM
Static draw
22.8533 in.wg

Duct and entrance

Duct velocity
13,781.5 FPM
Duct velocity pressure
11.8411 in.wg
Entry loss coefficient
0.93
Irrecoverable entry loss
11.0122 in.wg
Hood static suction magnitude
22.8533 in.wg

Worked calculation at the starting values

The squared distance term makes the remote source expensive to capture. Move the hood input closer and compare the flow.

  1. Reach area = 10 × 0.5334² + 0.2972897 in m².
  2. Required flow = 7.981811 m³/s at 2.54 m/s capture velocity with the entered hood geometry.
  3. Static suction = (1 + 0.93) × 2,949.478 = 5,692.492 Pa.
Starting result snapshot
Exhaust flow
16,912.5 CFM
Source speed
500 FPM
Face speed
5,285.16 FPM
Static draw
22.8533 in.wg

Equations and assumptions

Freestanding face

Q = k × V_c × (10 × X² + A)

DallaValle approximation with k = 1 for plain hoods and k = 0.75 for flanged hoods. Use ft, ft² and FPM for CFM, or m, m² and m/s for m³/s. The result is sensitive to the square of X.

Long slot

Q = V_c × max(A, k × 3.7 × L × X)

L is slot length. The line-sink relation suits a long, narrow opening. The model uses face area as a lower bound at very short distances. Compare A/L to the capture distance and use a slot-specific design for nonuniform slots.

Face and duct velocity

V_face = Q ÷ A · V_duct = Q ÷ (π × D² ÷ 4)

The target is measured at the source. The face and duct values answer different questions. Presets between 50 and 2,000 FPM are starting points for different source energies and crossdrafts.

Entry and static suction

VP = (FPM ÷ 4005)² · |SPₕ| = (1 + Fₕ) × VP

VP is in in.wg at standard air density. Irrecoverable entry loss equals Fₕ × VP. Static suction is shown as a magnitude. Auto Fₕ uses example coefficients 0.93 for plain and 0.49 for flanged openings.

References