Worked example · Warehouse planning

Mixed frozen distribution room

A four-level commercial freezer uses a daily load profile and regularly scheduled electric defrost.

Rack positions
1,576
Annual energy
563,453kWh/yr
Annual cost
81,701USD/yr
Peak draw
126.6kW
Edit inputs

Inputs

Edit any value to recalculate.

Storage footprint

Use one storage position footprint including the assigned rack clearance around the pallet.

m
m
m
m
m
%
m
m
Refrigeration load profile
kW
kW/TR
h/day
%
%
kW
days
Electric defrost & tariff

The currency changes the billing label. Enter the local rate per kWh in that currency.

kW
cycles/day
min
%
USD/kWh

Annual refrigeration electricity

Annual refrigeration electricityElectric heaters and the compressor work required to remove retained defrost heat appear as two separate energy uses.Energy use / kWh per operating yearBase compressor487,811Defrost heaters18,396Defrost recovery4,687Auxiliaries52,560Annual total563,453 kWh

Electric heaters and the compressor work required to remove retained defrost heat appear as two separate energy uses.

Calculation breakdown

Energy cost per position per month
4.32USD/position/mo
Usable rack levels
4
Positions per rack level
394
Net rack floor area
556.5m²
Equivalent full-load hours per day
15.3h/day
Base compressor electricity
487,811kWh/yr
Defrost heater electricity
18,396kWh/yr
Defrost heat returned to room
12,877kWhₜₕ/yr
Defrost recovery electricity
4,687kWh/yr
Auxiliary electricity
52,560kWh/yr
Defrost heater on-time
1.2h/day

Work through this case

  1. Defrost heater electricity 18,396kWh/yr
  2. Defrost recovery electricity 4,687kWh/yr
  3. Energy cost per position per month 4.32USD/position/mo

Compare direct heater electricity and compressor recovery electricity before estimating annual energy cost per position.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Rack positions

positions = floor(net area / pitch footprint) × min(planned, height-limited levels)

The area factor covers circulation and unavailable floor area. The clear height check uses the overhead clearance and rack level pitch. Verify rows, egress, fire protection, and structure separately.

Energy and defrost

kWh = base compressor + heater + defrost recovery + auxiliaries

Apply peak and off-peak load percentages over their daily hours. Heater kWh is power × cycles × cycle hours × days. Convert retained room heat into compressor recovery electricity at the entered kW/TR.

Peak and cost

annual cost = annual kWh × tariff • position cost = annual cost / (positions × 12)

Peak adds the compressor, active heater, and auxiliaries if they run together. With staging, the compressor draw must cover its daily energy and defrost recovery during the heater-off hours. If that requires more than rated draw, the staged peak is unavailable. The tariff estimate covers energy charges.

References

Questions and answers

What should I check in the mixed frozen distribution room example?

Compare direct heater electricity and compressor recovery electricity before estimating annual energy cost per position.