Input and output at one operating point
COP = Qevap / Wcomp • EER = 3.41214 × COP
These are compressor-boundary values. Use compressor power and evaporator heat removal measured or rated at the same condition.
Worked example · Equipment selection
An industrial ammonia refrigeration plant is screened at one specified load and condensing condition.
Edit any value to recalculate.
Heat absorbed at the evaporator and compressor electrical work combine at the condenser.
Use the water flow as a heat-balance estimate. The heat exchanger approach, pump duty, and system safety require separate checks.
Open a case with its assumptions loaded, then edit the inputs.
A walk-in cooler has a measured compressor input and enough airflow to evaluate a candidate condenser temperature rise.
A refrigeration plant rejects heat to a water loop with a specified supply-to-return rise.
A freezer load drives a low evaporating saturation temperature relative to the condenser.
A medium-temperature circuit runs with a lower condensing temperature during cool weather.
A storage room and coil run with a larger air-to-refrigerant temperature difference.
COP = Qevap / Wcomp • EER = 3.41214 × COP
These are compressor-boundary values. Use compressor power and evaporator heat removal measured or rated at the same condition.
TD = Tair,in − Tevap • COPCarnot = Tevap,K / (Tcond,K − Tevap,K)
TD describes the air-to-refrigerant difference at the evaporator. Carnot lift uses the two saturation temperatures, with an absolute cold-side temperature.
THR = Qevap + Wcomp • volume flow = THR / (ρ × cp × ΔT)
This screen assumes compressor input heat reaches the condenser. Air properties are 1.20 kg/m³ and 1.006 kJ/(kg·K). Water properties are 997 kg/m³ and 4.186 kJ/(kg·K).
Use the water flow as a heat-balance estimate. The heat exchanger approach, pump duty, and system safety require separate checks.
ColdChainLab · Engineering calculation
Metric SI · https://calcsheetlab.com/coldchainlab/evaporator-td-condenser-thr-cop/ammonia-plant-water-loop/
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.