Worked example · Equipment selection

Cool-weather floating head pressure

A medium-temperature circuit runs with a lower condensing temperature during cool weather.

Actual COP
4.14
Evaporator TD
8K
Heat rejected
72kW
EER
14.14BTU/(Wh)
Edit inputs

Inputs

Edit any value to recalculate.

Capacity & electrical input
kW
kW
Operating temperatures
°C
°C
°C
Heat-rejection medium

Air and water flows are alternatives at their entered temperature rises.

K
K

Refrigeration-cycle energy flow

Refrigeration-cycle energy flowHeat absorbed at the evaporator and compressor electrical work combine at the condenser.Evaporator58 kW-4 °C saturationCompressor14 kWElectrical inputCondenser72 kW27 °C saturationExpansion valvePressure dropsLiquid to two-phaseCold-side heatHeat rejection

Heat absorbed at the evaporator and compressor electrical work combine at the condenser.

Calculation breakdown

Carnot refrigeration COP
8.68
Fraction of Carnot COP
47.7%
Condenser air volume flow
26,839m³/h
Condenser water volume flow
188.2L/min
Saturation temperature lift
31K
Net refrigeration capacity
16.49TR

Work through this case

  1. Carnot refrigeration COP 8.68
  2. Actual COP 4.14
  3. EER 14.14BTU/(Wh)

A smaller lift raises the theoretical COP. Use actual power and capacity for the floating-head operating point before estimating savings.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Input and output at one operating point

COP = Qevap / Wcomp • EER = 3.41214 × COP

These are compressor-boundary values. Use compressor power and evaporator heat removal measured or rated at the same condition.

Temperature difference & ideal limit

TD = Tair,in − Tevap • COPCarnot = Tevap,K / (Tcond,K − Tevap,K)

TD describes the air-to-refrigerant difference at the evaporator. Carnot lift uses the two saturation temperatures, with an absolute cold-side temperature.

Condenser heat rejection

THR = Qevap + Wcomp • volume flow = THR / (ρ × cp × ΔT)

This screen assumes compressor input heat reaches the condenser. Air properties are 1.20 kg/m³ and 1.006 kJ/(kg·K). Water properties are 997 kg/m³ and 4.186 kJ/(kg·K).

References

Questions and answers

What should I check in the cool-weather floating head pressure example?

A smaller lift raises the theoretical COP. Use actual power and capacity for the floating-head operating point before estimating savings.