Freeze: mass concentration table • Burst: volume concentration table
Freeze is the onset of ice in an inhibited solution. Burst is a shutdown reference that assumes space for expansion. A ≤ marker gives the coldest applicable table bound, or the colder freeze point when the applicable freeze point is below that bound. Confirm with the selected fluid supplier.
Density, specific heat, and viscosity use offline aqueous glycol fits at the mean fluid temperature. Properties vary with inhibitor package. Flow is unavailable when the cold leg reaches the freeze point.
Water reference properties are at 20 °C. The pressure factor compares fully developed laminar flow in the same pipe at the resized flow. Turbulent pipe, coil, and fitting losses need their own hydraulic calculations.
What should I check in the low-temperature ethylene glycol loop example?
Verify ethylene glycol is permitted for the application and compare the rising viscosity with equipment and piping data.
ColdChainLab · Engineering calculation
Low-temperature ethylene glycol loop
Metric SI · https://calcsheetlab.com/coldchainlab/glycol-brine-freeze-flow/ethylene-glycol-low-temperature/
Inputs
Glycol type
Ethylene glycol
Concentration by weight
55 %
Mean operating fluid temp.
-24 °C
Target cooling load
100 kW
Return-to-supply rise
5.5 K
Results
Freeze point
-41.1°C
Burst limit
≤ -45.6°C
Required flow
341.1L/min
Laminar ΔP
45.85×
Specific heat
2.932kJ/(kg·K)
Specific-heat ratio to water
0.701×
Fluid density
1,090.7kg/m³
Specific gravity (water at 20 °C)
1.093
Required flow vs water
1.305×
Dynamic viscosity
35.19mPa·s
Same-flow laminar pressure factor
35.12×
Supply leg margin above freeze
14.4K
Estimated supply temperature
-26.8°C
Approximate volume concentration
53.4%
Ethylene glycol is toxic. Confirm which inhibited fluid and materials are allowed for the application.
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.