Worked example · Secondary loops

Winter shutdown burst screen

A winterized secondary loop is evaluated for first ice and at-rest burst protection using two separate thresholds.

Freeze point
-17.9°C
Burst limit
≤ -45.6°C
Required flow
50.7L/min
Laminar ΔP
4.75×
Edit inputs

Inputs

Edit any value to recalculate.

Secondary coolant

Concentration is mass percent of glycol in the solution.

%
°C
Loop duty

The cold supply leg is the mean operating temperature minus half the loop rise.

kW
K

Ethylene glycol is toxic. Confirm which inhibited fluid and materials are allowed for the application.

Freeze point and flow correction

Freeze point and flow correctionThe flow correction curve starts where the estimated cold supply leg stays liquid at the selected duty.Freeze / °CGlycol concentration / wt %015304560-55-36-172Flow / ×0.951.081.221.35Freeze pointRequired flow factor

The flow correction curve starts where the estimated cold supply leg stays liquid at the selected duty.

Calculation breakdown

Specific heat
3.563kJ/(kg·K)
Specific-heat ratio to water
0.852×
Fluid density
1,051.4kg/m³
Specific gravity (water at 20 °C)
1.053
Required flow vs water
1.114×
Dynamic viscosity
4.27mPa·s
Same-flow laminar pressure factor
4.26×
Supply leg margin above freeze
18.9K
Estimated supply temperature
1°C
Approximate volume concentration
33.1%

Work through this case

  1. Approximate volume concentration 33.1%
  2. Freeze point -17.9°C
  3. Burst limit ≤ -45.6°C

A burst bound assumes room for expansion. The same concentration must still satisfy a separate first-ice margin during operation.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Freeze and burst protection

Freeze: mass concentration table • Burst: volume concentration table

Freeze is the onset of ice in an inhibited solution. Burst is a shutdown reference that assumes space for expansion. A ≤ marker gives the coldest applicable table bound, or the colder freeze point when the applicable freeze point is below that bound. Confirm with the selected fluid supplier.

Sensible cooling flow

L/min = 60,000 × Q(kW) / [ρ(kg/m³) × cp(kJ/(kg·K)) × ΔT(K)]

Density, specific heat, and viscosity use offline aqueous glycol fits at the mean fluid temperature. Properties vary with inhibitor package. Flow is unavailable when the cold leg reaches the freeze point.

Water-reference derating

Kflow = (ρcp)water / (ρcp)glycol • KΔP,laminar = (μglycol / μwater) × Kflow

Water reference properties are at 20 °C. The pressure factor compares fully developed laminar flow in the same pipe at the resized flow. Turbulent pipe, coil, and fitting losses need their own hydraulic calculations.

References

Questions and answers

What should I check in the winter shutdown burst screen example?

A burst bound assumes room for expansion. The same concentration must still satisfy a separate first-ice margin during operation.