Worked example · Commodity storage

High-humidity broccoli head storage

Whole broccoli heads are held in a humid room after cooling, with respiration estimated from head data.

Resp. heat
238.2W
Vapor deficit
0.023kPa
Weight loss
1.35%
Coil TD band
2.8–3.9K
Edit inputs

Inputs

Edit any value to recalculate.

Commodity & storage

Use a weight-loss coefficient for the packaging, maturity, and airflow of the lot.

kg
°C
%
days
%/(kPa·day)

The default moisture-loss coefficient is illustrative. Calibrate it for the commodity, packaging, and airflow.

Respiration heat by storage temperature

Respiration heat by storage temperatureThe marker shows the selected temperature on the commodity curve when published points bracket it.Respiration / W per tonneStorage temperature / °C051015200331662993Respiration curveOperating point

The marker shows the selected temperature on the commodity curve when published points bracket it.

Calculation breakdown

Respiration heat per stored ton
85.1W/t
Respiration rate
14.4mL CO₂/(kg·h)
Initial moisture loss per day
0.341%
Moisture mass lost
37.9kg
Estimated remaining mass
2,762.1kg

Work through this case

  1. Respiration rate 14.4mL CO₂/(kg·h)
  2. Resp. heat 238.2W
  3. Weight loss 1.35%

Keep the whole-head and cut-floret cases separate. Processing can change respiration, and packaging can change the effective shrink coefficient.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Respiration heat

q (W/t) = respiration rate × 122 × 4,184 / 86,400

Presets use the midpoint of the UC Davis CO₂-rate ranges in mL/(kg·h), interpolated with temperature. The metric heat basis is one tonne. The US readout uses a 2,000 lb short ton. Custom mode uses rate = reference rate × Q₁₀^[(T − Tref)/10].

Vapor pressure deficit

VPD = 0.6108 × exp[17.27T / (T + 237.3)] × (1 − RH)

Use T in °C and RH as a fraction. The model treats the produce surface as saturated at room temperature.

Weight loss & coil selection

m(t) = m₀ × exp[−k × VPD × days / 100]

Apple, early potato, and lettuce coefficients use ASHRAE tabulated reference values or close commodity proxies. The strawberry and broccoli coefficients are illustrative. The TD bands reflect high-humidity starting points. Confirm coil, airflow, control, and packaging effects with the supplier.

References

Questions and answers

What should I check in the high-humidity broccoli head storage example?

Keep the whole-head and cut-floret cases separate. Processing can change respiration, and packaging can change the effective shrink coefficient.