Worked example · Commodity storage

Custom produce respiration curve

A measured commodity rate at a reference temperature is combined with an estimated Q₁₀ for sensitivity analysis.

Resp. heat
263.2W
Vapor deficit
0.075kPa
Weight loss
1.56%
Coil TD band
3.9–5K
Edit inputs

Inputs

Edit any value to recalculate.

Commodity & storage

Use a weight-loss coefficient for the packaging, maturity, and airflow of the lot.

kg
°C
%
days
%/(kPa·day)
Custom respiration curve
mL CO₂/(kg·h)
°C
×

Respiration heat by storage temperature

Respiration heat by storage temperatureThe marker shows the selected temperature on the commodity curve when published points bracket it.Respiration / W per tonneStorage temperature / °C05101520079158236Respiration curveOperating point

The marker shows the selected temperature on the commodity curve when published points bracket it.

Calculation breakdown

Respiration heat per stored ton
79.8W/t
Respiration rate
13.5mL CO₂/(kg·h)
Initial moisture loss per day
0.263%
Moisture mass lost
51.6kg
Estimated remaining mass
3,248.4kg

Work through this case

  1. Respiration rate 13.5mL CO₂/(kg·h)
  2. Respiration heat per stored ton 79.8W/t
  3. Weight loss 1.56%

Vary Q₁₀ when testing warmer storage. The custom loss coefficient should come from mass checks at known temperature and humidity.

More worked examples

Open a case with its assumptions loaded, then edit the inputs.

Open base calculator

Formulas and assumptions

Respiration heat

q (W/t) = respiration rate × 122 × 4,184 / 86,400

Presets use the midpoint of the UC Davis CO₂-rate ranges in mL/(kg·h), interpolated with temperature. The metric heat basis is one tonne. The US readout uses a 2,000 lb short ton. Custom mode uses rate = reference rate × Q₁₀^[(T − Tref)/10].

Vapor pressure deficit

VPD = 0.6108 × exp[17.27T / (T + 237.3)] × (1 − RH)

Use T in °C and RH as a fraction. The model treats the produce surface as saturated at room temperature.

Weight loss & coil selection

m(t) = m₀ × exp[−k × VPD × days / 100]

Apple, early potato, and lettuce coefficients use ASHRAE tabulated reference values or close commodity proxies. The strawberry and broccoli coefficients are illustrative. The TD bands reflect high-humidity starting points. Confirm coil, airflow, control, and packaging effects with the supplier.

References

Questions and answers

What should I check in the custom produce respiration curve example?

Vary Q₁₀ when testing warmer storage. The custom loss coefficient should come from mass checks at known temperature and humidity.