Presets use the midpoint of the UC Davis CO₂-rate ranges in mL/(kg·h), interpolated with temperature. The metric heat basis is one tonne. The US readout uses a 2,000 lb short ton. Custom mode uses rate = reference rate × Q₁₀^[(T − Tref)/10].
Use T in °C and RH as a fraction. The model treats the produce surface as saturated at room temperature.
Weight loss & coil selection
m(t) = m₀ × exp[−k × VPD × days / 100]
Apple, early potato, and lettuce coefficients use ASHRAE tabulated reference values or close commodity proxies. The strawberry and broccoli coefficients are illustrative. The TD bands reflect high-humidity starting points. Confirm coil, airflow, control, and packaging effects with the supplier.
What should I check in the custom produce respiration curve example?
Vary Q₁₀ when testing warmer storage. The custom loss coefficient should come from mass checks at known temperature and humidity.
ColdChainLab · Engineering calculation
Custom produce respiration curve
Metric SI · https://calcsheetlab.com/coldchainlab/produce-respiration-weight-loss/custom-mixed-produce-rate/
Inputs
Commodity
Custom commodity
Stored product mass
3300 kg
Storage temperature
8 °C
Storage relative humidity
93 %
Storage duration
6 days
Effective moisture-loss coefficient
3.5 %/(kPa·day)
Reference respiration rate
9 mL CO₂/(kg·h)
Reference temperature
3 °C
Q₁₀ for a 10 K rise
2.25 ×
Results
Resp. heat
263.2W
Vapor deficit
0.075kPa
Weight loss
1.56%
Coil TD band
3.9–5K
Respiration heat per stored ton
79.8W/t
Respiration rate
13.5mL CO₂/(kg·h)
Initial moisture loss per day
0.263%
Moisture mass lost
51.6kg
Estimated remaining mass
3,248.4kg
Use these estimates for preliminary engineering. Verify results against validated cold-chain qualification protocols, applicable ASHRAE Standards 15 and 34, and local food and pharmaceutical regulations. Use manufacturer data, measured operating conditions, and approved acceptance criteria before acting on a result.