ControlLoopLab
Home CalculatorsLoop design

Bode gain & phase margins

Check unity and phase crossovers for a two-pole open-loop model with integrators, an optional zero and transport delay.

Model inputs

Open-loop plant
rad/s
rad/s
s
Lead zero

Open-loop Bode plot

Stable
Phase margin
37.468°
Gain margin
11.561dB
Gain crossover
25.961rad/s
Delay margin
0.025189s
Bode magnitude and phaseLoop magnitudedB3.2512.447.7183700−74.2−40.4−6.527.4Frequency (rad/s, log)Unwrapped phasedeg3.2512.447.7183700−355−263−171−78.4Frequency (rad/s, log)ωgc / PM arrowωpc / GM arrow
L(s) = K(1 + s/ωz) exp(−sθ) / [sⁿ(1 + s/ωp1)(1 + s/ωp2)]

Calculated results

Gain crossover ωgc
25.961rad/s
Phase margin
37.468°
Phase crossover ωpc
57.702rad/s
Gain margin
11.561dB
Gain margin ratio
3.7849×
Added delay margin
0.025189s
Finite unity crossings
1
Nyquist RHP pole count
0
  • For multiple odd-180° crossings, the reported gain margin is the one closest to 0 dB.

Model and interpretation

Full methodology

Check the open-loop model

Assumes unity negative feedback, two stable real poles, a positive gain and an optional left-half-plane zero. Phase is unwrapped analytically, including the linear delay term. The logarithmic chart is for inspection. Crossovers are root-refined at full precision.

Interpret crossovers together

The Nyquist count uses odd-180° crossings where loop gain exceeds unity. Without delay, the Routh criterion gives the stability boundary directly. An odd-180° unity crossing places a pole on the imaginary axis and other unstable poles can coexist. The reported gain margin is closest to 0 dB. A positive added-delay allowance is meaningful only when the current loop is stable.

Apply the screening thresholds

A stable model with phase margin below 30° or gain margin below 6 dB is marked marginal. A negative delay margin describes the signed reserve at the quoted crossover. Inspect the full measured loop for uncertainty, extra poles and nonlinear constraints.