Calculation methods
Review the equations, numerical methods, units and limits behind each ControlLoopLab model.
FOPDT tuning & controller forms
The simulation uses a signed first-order process gain, one real lag and pure transport delay. Parallel gains follow Kp = Kc, Ki = Kc/Ti and Kd = Kc Td. For interacting gains, expand the two controller factors and equate the proportional, integral and derivative terms. The displayed forms are equivalent before derivative filtering.
Controller forms follow Åström and Hägglund, PID Controllers: Theory, Design, and Tuning (ISA, 1995). Tuning references include Skogestad (DOI 10.1016/S0959-1524(02)00062-8), Grimholt and Skogestad (DYCOPS 2013), Rivera et al. (DOI 10.1021/i200032a041), Ziegler and Nichols (1942), and Cohen and Coon (DOI 10.1115/1.4015451).
Transient shape & robustness
The second-order step uses the analytic pole response, including the repeated-root limit at ζ = 1. Settling locates the last tolerance exit, with an envelope estimate only when the number of oscillations exceeds a trillion. The synthesis target uses 4/(ζωn).
The Bode tool brackets and refines crossover roots across monotone intervals. Summing signed odd-180° crossings at gain above unity yields the Nyquist winding, accounting for the integrators at the origin. This counts unstable poles for the stated model. See Åström and Murray, Feedback Systems, second edition, for time response, Nyquist and loop shaping.
Discrete frequency & normalization
The low-pass and compensator calculations use normalized a0 = 1 with subtractive feedback coefficients. Bilinear prewarping matches the named cutoff or center at the sample rate. DTFT evaluation uses the factored transfer function so rounding of nearly canceling polynomial terms does not dominate the readout.
Noise bandwidth integrates squared gain from DC to one-sided Nyquist. The ADC uses full-scale sine RMS as the reference for ENOB (Analog Devices MT-003). Aliases are wrapped into the first half of the sample spectrum.
Field sensor models
IEC 60751:2022 provides the nominal platinum resistance–temperature function. Temperature and temperature differences use separate unit conversions. Fractional AWG values represent the equivalent copper area in the standard logarithmic gauge series.
Transmitter budget is evaluated at 22 mA. The NE 43 screening bands and device alarm thresholds should be checked separately. Emerson Rosemount 644R documentation (00813-0300-4728) illustrates a device with selectable alarm limits.