Bode gain & phase margins
Check unity and phase crossovers for a two-pole open-loop model with integrators, an optional zero and transport delay.
Model inputs
- Open-loop gain K
- 34
- Integrators
- Type 1 · one
- First pole ωp1
- 32 rad/s
- Second pole ωp2
- 140 rad/s
- Transport delay θ
- 0.002 s
- Real zero
- Disabled
Model inputs
Open-loop Bode plot
Stable- Phase margin
- 37.468°
- Gain margin
- 11.561dB
- Gain crossover
- 25.961rad/s
- Delay margin
- 0.025189s
Calculated results
- Gain crossover ωgc
- 25.961rad/s
- Phase margin
- 37.468°
- Phase crossover ωpc
- 57.702rad/s
- Gain margin
- 11.561dB
- Gain margin ratio
- 3.7849×
- Added delay margin
- 0.025189s
- Finite unity crossings
- 1
- Nyquist RHP pole count
- 0
- For multiple odd-180° crossings, the reported gain margin is the one closest to 0 dB.
Model and interpretation
Full methodologyCheck the open-loop model
Assumes unity negative feedback, two stable real poles, a positive gain and an optional left-half-plane zero. Phase is unwrapped analytically, including the linear delay term. The logarithmic chart is for inspection. Crossovers are root-refined at full precision.
Interpret crossovers together
The Nyquist count uses odd-180° crossings where loop gain exceeds unity. Without delay, the Routh criterion gives the stability boundary directly. An odd-180° unity crossing places a pole on the imaginary axis and other unstable poles can coexist. The reported gain margin is closest to 0 dB. A positive added-delay allowance is meaningful only when the current loop is stable.
Apply the screening thresholds
A stable model with phase margin below 30° or gain margin below 6 dB is marked marginal. A negative delay margin describes the signed reserve at the quoted crossover. Inspect the full measured loop for uncertainty, extra poles and nonlinear constraints.