Trace what each model measures, where its assumptions apply, and which limits need a datasheet or field measurement.
Power and distance
Enter power relative to one milliwatt in dBm. Enter attenuation and allowances as positive dB deductions. We add physical component losses first, then subtract the entered engineering reserve from the budget. Overload uses the high launch and the physical path. Metric and US views convert from the same stored engineering values.
Channel and plant limits
Check dispersion against transceiver tolerances, modal reach against an Ethernet PHY and WDM plans against the optics and filters. Replace planning values with measured bore, cable ratings, power and plant loss. An OTDR trace helps locate events. An optical source and power meter measure end-to-end insertion loss.
G.652 identifies single-mode fiber characteristics at telecom wavelengths. The 850 and 1300 nm multimode presets and component losses are editable planning inputs. Use measured loss or cable and interface datasheets for acceptance under ANSI/TIA-568.3-E.
B+ and C+ follow the G.984.2/G.9807.1 class-window convention. N1 and N2 use the G.9807.1 basic wavelength set. C++ is a vendor profile. PX20 uses the EPON planning window. The TX/RX entries are editable presets and the route cap represents an entered equipment limit. Verify wavelength plans, splitters, differential reach and equipment interoperability separately.
The G.652.D example uses a representative 17 ps/(nm·km) at 1550 nm. G.655 shifts dispersion to a nonzero value in that band, represented here by an editable +4. Use equipment-specific tolerance and PMD outage limits for coherent, PAM4 and other nonbinary links.
Laser class comes from the equipment marking and applicable accessible emission limits. A separate +10 dBm composite advisory highlights elevated optical power for review. IEC Class 1M and Class 3B handling depends on the marked class and accessible emission conditions.
The SMF-28 and OM4 indices are illustrative group index presets. Real dead zones depend on reflectance, receiver saturation, instrument processing and test setup. Treat calculated EDZ and ADZ as estimates and check actual instrument specifications and traces.
G.694.1 defines the fixed DWDM grid around 193.1 THz. The C-band endpoints used here define the calculator’s scope. G.694.2 defines nominal CWDM centers at 20 nm increments from 1271 through 1611 nm.
The 850 nm planning table uses IEEE 802.3 Clauses 38, 52, 86, 95, 112 and 138 with manufacturer guidance for OM5. The original Gigabit SX table predates OM3 through OM5. This calculator uses the conservative OM2 envelope for those grades. For newer 850 nm PHYs, OM5 uses the corresponding OM4 planning values. Check the optic for vendor-specific distances and any lane skew or return-loss requirements.
EMT uses nominal planning bores. The Schedule 40 PVC presets use minimum electrical-conduit bores from the linked CANTEX drawing. HDPE uses IPS SDR 13.5 geometry before wall tolerances. Enter the actual product bore and verify the locally adopted code. The initial 600 lbf threshold is about 2,669 N. Some cable sheets specify 2,700 N separately. Enter the actual cable or pulling assembly rating and plan complex or inclined pulls section by section.