100GBASE-SR4 OM4 data center run

An 87 m channel with two connector pairs and two splices per lane.

Inputs

Enter the installed length and count mated pairs and splices on one optical lane. Use measured component losses where available.

Ethernet channel
m
dB/km
Connections and splices
dB
dB
LIVE ANATOMY

Reach by OM fiber grade

Reach by OM fiber gradeMAX REACH100mSPAN LOSS1.161dBLOSS MARGIN0.739dBMODAL BW4,700MHz·km100GBASE-SR4Run 87 mOM1N/AOM2N/AOM370 mOM4100 mOM5100 m0105 mCHANNEL LOSS MARGIN0 dB1.9 dB limit0.74 dB left
PassThe span meets the selected PHY’s distance and insertion-loss limits.

Modal bandwidth and reach

850 nm modal bandwidth–distance product
4,700 MHz·km
Estimated modal bandwidth at span
54.023 GHz
Installed span
87 m
PHY grade reach limit
100 m

Per-lane insertion loss

Fiber attenuation
0.261 dB
Connector plus splice loss
0.9 dB
Estimated channel insertion loss
1.161 dB
Maximum channel insertion loss
1.9 dB
Connector and splice allowance
1.639 dB
Remaining insertion-loss margin
0.739 dB

What to check

Use the remaining connector and splice allowance to check patching changes.

Open the general multimode ethernet reach calculator

Formulas and assumptions

Modal-bandwidth comparison

Bandwidth estimate (MHz) = bandwidth–distance product / L(km)

OM1 and OM2 use the 850 nm overfilled launch value. OM3 through OM5 use effective modal bandwidth at 850 nm. The estimate illustrates scaling with distance.

Optical channel loss

Lchannel = α × L(km) + npairs × Lpair + nsplices × Lsplice

Compare installed loss with the selected PHY and grade’s channel allowance. The connector and splice allowance is the channel limit minus fiber loss.

Reach screen

Pass when length ≤ PHY reach and Lchannel ≤ PHY loss limit

The comparison uses tabulated values. A fiber grade without a supported entry requires separate transceiver data.

The 850 nm planning table uses IEEE 802.3 Clauses 38, 52, 86, 95, 112 and 138 with manufacturer guidance for OM5. The original Gigabit SX table predates OM3 through OM5. This calculator uses the conservative OM2 envelope for those grades. For newer 850 nm PHYs, OM5 uses the corresponding OM4 planning values. Check the optic for vendor-specific distances and any lane skew or return-loss requirements.