10GBASE-SR at the OM2 reach limit

Check an 82 m OM2 channel at its reference distance.

Inputs

Enter the installed length and count mated pairs and splices on one optical lane. Use measured component losses where available.

Ethernet channel
m
dB/km
Connections and splices
dB
dB
LIVE ANATOMY

Reach by OM fiber grade

Reach by OM fiber gradeMAX REACH82mSPAN LOSS1.646dBLOSS MARGIN0.654dBMODAL BW500MHz·km10GBASE-SRRun 82 mOM133 mOM282 mOM3300 mOM4400 mOM5400 m0420 mCHANNEL LOSS MARGIN0 dB2.3 dB limit0.65 dB left
PassThe span meets the selected PHY’s distance and insertion-loss limits.

Modal bandwidth and reach

850 nm modal bandwidth–distance product
500 MHz·km
Estimated modal bandwidth at span
6.0976 GHz
Installed span
82 m
PHY grade reach limit
82 m

Per-lane insertion loss

Fiber attenuation
0.246 dB
Connector plus splice loss
1.4 dB
Estimated channel insertion loss
1.646 dB
Maximum channel insertion loss
2.3 dB
Connector and splice allowance
2.054 dB
Remaining insertion-loss margin
0.654 dB

What to check

At the exact distance limit, the channel still needs to pass the loss screen.

Open the general multimode ethernet reach calculator

Formulas and assumptions

Modal-bandwidth comparison

Bandwidth estimate (MHz) = bandwidth–distance product / L(km)

OM1 and OM2 use the 850 nm overfilled launch value. OM3 through OM5 use effective modal bandwidth at 850 nm. The estimate illustrates scaling with distance.

Optical channel loss

Lchannel = α × L(km) + npairs × Lpair + nsplices × Lsplice

Compare installed loss with the selected PHY and grade’s channel allowance. The connector and splice allowance is the channel limit minus fiber loss.

Reach screen

Pass when length ≤ PHY reach and Lchannel ≤ PHY loss limit

The comparison uses tabulated values. A fiber grade without a supported entry requires separate transceiver data.

The 850 nm planning table uses IEEE 802.3 Clauses 38, 52, 86, 95, 112 and 138 with manufacturer guidance for OM5. The original Gigabit SX table predates OM3 through OM5. This calculator uses the conservative OM2 envelope for those grades. For newer 850 nm PHYs, OM5 uses the corresponding OM4 planning values. Check the optic for vendor-specific distances and any lane skew or return-loss requirements.

Worked examples

Open a scenario and edit any parameter.