NFPA 2001 · Worked example
Altitude-corrected FK-5-1-12 quantity
A protected enclosure at 5,200 ft elevation uses a 5.3% listed design basis. The minimum enclosure temperature is 50 °F.
Inputs
Clean-agent enclosure section
Edit inputsThe modeled concentration and positive vent area clear the entered checks. Confirm listed design and exposure provisions.
How to read this example
Use the atmospheric factor to adjust the sea-level dose. Recheck rounded charge and exposure at the higher temperature.
Open the base calculatorCalculated values
- Atmosphere-corrected design mass
- 451.36 lb
- Specific vapor volume at design temperature
- 1.1075 ft³/lb
- Atmospheric correction factor
- 0.812
- Estimated cylinder count
- 5
- Installed charge at full entered fill
- 500 lb
- IG-541 free gas at 70 °F / 21 °C
- Inert gas only
- Installed concentration at minimum temperature
- 5.84 %
- Installed concentration at maximum temperature
- 6.25 %
- Equivalent oxygen at sea level
- Inert gas only
- No-effect exposure reference
- 10 %
- Low-effect exposure reference
- >10% (lower bound)
- Margin to no-effect reference
- 3.75 pp
- Estimated required clear vent area
- 2.05 ft²
- Modeled positive peak pressure
- 0.51 psf
- Clear vent area reserve
- 4.95 ft²
Equations and assumptions
Halocarbon W = (V/S) [C/(100 − C)] × f_atmIG-541 X = 2.303 (V_s/S) log₁₀[100/(100 − C)]IG-541 free gas = room volume × X × f_atmA_vent ≈ Q_peak / [C_d √(2 ΔP/ρ_air)]
Enter the design concentration from the listing. Required mass uses the minimum temperature and interpolated atmospheric correction. Exposure uses the full rounded cylinder charge at maximum temperature. For IG-541, the exposure bar uses sea-level equivalent oxygen expressed as equivalent agent concentration.
The exposure references screen concentration only. Honor current NFPA 2001 exposure time and egress provisions. Use the listed system design, enclosure integrity testing and the agent-specific safety data.
The vent estimate is a quasi-steady positive-pressure air-orifice calculation. It uses the entered peak factor and assumes an open vent. The model screens peak pressures up to 5% of ambient pressure. It omits negative transients, vent opening pressure, humidity and manufacturer-specific discharge profiles.