NFPA 2001 · Worked example

IG-541 with limited clear opening

A 14,000 ft³ enclosure has 1.5 ft² of clear opening and a 4 psf positive pressure limit. The IG-541 input uses a 60-second discharge.

Inputs

Agent and enclosure
ft³
%

Enter the listed concentration for the fuel and system.

°F
°F
ft
lb

Use usable agent mass, including for IG-541.

Positive-pressure vent screen
s
psf
ft²

Clean-agent enclosure section

Worksheet units
Edit inputs
Clean-agent enclosure section · Input-linked engineering diagramAGENT MASS558.63lbCYLINDERS10PEAK CONC.36.84%VENT AREA5.87ft²IG-541ROOM 14,000 ft³10 CYLFree vent 1.5 ft²Modeled full-charge exposure36.84%0%43% NOAEL52% LOAEL
Positive vent area shortfall

The assumed open area is smaller than the area predicted by the positive-pressure model.

How to read this example

The positive pressure screen compares modeled area with the available opening. Use transient manufacturer data and enclosure strength to design an actual vent.

Open the base calculator

Calculated values

Atmosphere-corrected design mass
558.63 lb
Specific vapor volume at design temperature
11.1866 ft³/lb
Atmospheric correction factor
1
Estimated cylinder count
10
Installed charge at full entered fill
560 lb
IG-541 free gas at 70 °F / 21 °C
6,344.92 ft³
Installed concentration at minimum temperature
36.08 %
Installed concentration at maximum temperature
36.84 %
Equivalent oxygen at sea level
13.2 %
No-effect exposure reference
43 %
Low-effect exposure reference
52 %
Margin to no-effect reference
6.16 pp
Estimated required clear vent area
5.87 ft²
Modeled positive peak pressure
61.16 psf
Clear vent area reserve
-4.37 ft²

Equations and assumptions

  • Halocarbon W = (V/S) [C/(100 − C)] × f_atm
  • IG-541 X = 2.303 (V_s/S) log₁₀[100/(100 − C)]
  • IG-541 free gas = room volume × X × f_atm
  • A_vent ≈ Q_peak / [C_d √(2 ΔP/ρ_air)]

Enter the design concentration from the listing. Required mass uses the minimum temperature and interpolated atmospheric correction. Exposure uses the full rounded cylinder charge at maximum temperature. For IG-541, the exposure bar uses sea-level equivalent oxygen expressed as equivalent agent concentration.

The exposure references screen concentration only. Honor current NFPA 2001 exposure time and egress provisions. Use the listed system design, enclosure integrity testing and the agent-specific safety data.

The vent estimate is a quasi-steady positive-pressure air-orifice calculation. It uses the entered peak factor and assumes an open vent. The model screens peak pressures up to 5% of ambient pressure. It omits negative transients, vent opening pressure, humidity and manufacturer-specific discharge profiles.