A 14,000 ft³ enclosure has 1.5 ft² of clear opening and a 4 psf positive pressure limit. The IG-541 input uses a 60-second discharge.
Inputs
Clean-agent enclosure section
Edit inputsThe assumed open area is smaller than the area predicted by the positive-pressure model.
How to read this example
The positive pressure screen compares modeled area with the available opening. Use transient manufacturer data and enclosure strength to design an actual vent.
Open the base calculatorCalculated values
- Atmosphere-corrected design mass
- 558.63 lb
- Specific vapor volume at design temperature
- 11.1866 ft³/lb
- Atmospheric correction factor
- 1
- Estimated cylinder count
- 10
- Installed charge at full entered fill
- 560 lb
- IG-541 free gas at 70 °F / 21 °C
- 6,344.92 ft³
- Installed concentration at minimum temperature
- 36.08 %
- Installed concentration at maximum temperature
- 36.84 %
- Equivalent oxygen at sea level
- 13.2 %
- No-effect exposure reference
- 43 %
- Low-effect exposure reference
- 52 %
- Margin to no-effect reference
- 6.16 pp
- Estimated required clear vent area
- 5.87 ft²
- Modeled positive peak pressure
- 61.16 psf
- Clear vent area reserve
- -4.37 ft²
Equations and assumptions
Halocarbon W = (V/S) [C/(100 − C)] × f_atmIG-541 X = 2.303 (V_s/S) log₁₀[100/(100 − C)]IG-541 free gas = room volume × X × f_atmA_vent ≈ Q_peak / [C_d √(2 ΔP/ρ_air)]
Enter the design concentration from the listing. Required mass uses the minimum temperature and interpolated atmospheric correction. Exposure uses the full rounded cylinder charge at maximum temperature. For IG-541, the exposure bar uses sea-level equivalent oxygen expressed as equivalent agent concentration.
The exposure references screen concentration only. Honor current NFPA 2001 exposure time and egress provisions. Use the listed system design, enclosure integrity testing and the agent-specific safety data.
The vent estimate is a quasi-steady positive-pressure air-orifice calculation. It uses the entered peak factor and assumes an open vent. The model screens peak pressures up to 5% of ambient pressure. It omits negative transients, vent opening pressure, humidity and manufacturer-specific discharge profiles.