GroundGridLab · Lee · legacy IEEE 1584
Open-air Lee yard sensitivity
An outdoor 4.16 kV three-phase fault is used as an open-air Lee example at a 1.2 m working distance.
Above thermal boundary level. Preliminary estimate at the working position. PPE category requires the separate NFPA 70E table method.
- Incident energy
- 5.9405 J/cm²
- Arc-flash boundary
- 1,305.3 mm
- Time to boundary level
- 0.10142 s
- Working distance
- 1,200 mm
Inputs
| Equipment model | Open air · Lee |
|---|---|
| System line-to-line voltage | 4.16 kV |
| Three-phase bolted fault current | 8 kA |
| Arc clearing time | 0.12 s |
| Working distance from arc | 1,200 mm |
Derived values
| Energy in both systems | 1.4198 cal/cm² / 5.9405 J/cm² |
|---|---|
| Reference energy bracket | ≤ 4 cal/cm² |
| NFPA 70E PPE category | Separate equipment tables |
| Boundary reference | 5.021 J/cm² |
| Clearing ceiling at 8 cal/cm² | 0.67615 s |
| Clearing ceiling at 40 cal/cm² | 3.3807 s |
| Legacy arcing current | Open-air Lee model |
| Distance exponent | 2 |
Preliminary screening only. Use an IEEE 1584-2018 study, actual protective-device coordination and a qualified NFPA 70E assessment for equipment labeling, PPE or energized-work decisions.