Standards & model assumptions

Calculation Methods & Standards

Equations, editions, assumptions and applicability for each GroundGridLab electrical screening worksheet.

Step & Touch Voltage

IEEE Std 80-2013 §§6.1–6.2, 7.4 and 8.3 (equations 27–33). The tolerable body current is 0.116/√t for 50 kg and 0.157/√t for 70 kg. Multiply by (1,000 + 6Cₛρₛ) for step or (1,000 + 1.5Cₛρₛ) for touch.

The cover factor is Cₛ = 1 − 0.09(1 − ρ/ρₛ)/(2hₛ + 0.09), with hₛ in metres. Zero thickness uses Cₛ = 1 and the native soil resistivity in both limits. When ρₛ < ρ, the formal expression is shown for reference and the screen is marked for review because the surface potentials can change.

The clearing-time check inverts the selected limits with candidate voltages held constant. Available headroom uses the lesser of the calculated ceiling and 3 s. A calculated ceiling shorter than 0.03 s is outside the model range.

Open calculator

Substation Ground Grid

IEEE Std 80-2013 §§14.2, 15 and 16.5 (equations 55–57 and 85–99). The Sverak estimate adds the inverse buried length term to a depth-corrected plate term. Laurent–Niemann adds ρ/Lₜ to the zero-depth circular-plate estimate ρ√(π/A)/4.

Iɢ = IꜰSꜰDꜰ, and GPR = IɢRɢ relative to remote earth. GPR above the touch limit triggers a closer look at local and transferred potentials.

Each dimension is divided into enough equal bays to stay at or below the requested pitch. Use the larger actual pitch in Kₘ and the smaller in Kₛ as a rectangular-spacing approximation. Kᵢ = 0.644 + 0.148n. The mesh and step voltages equal ρIɢKᵢ times Kₘ/Lₘ and Kₛ/Lₛ, respectively.

Corner/perimeter rods use Kᵢᵢ = 1 and the enhanced Lₘ of Eq. 96. Lₛ = 0.75L꜀ + 0.85Lᵣ. Strongly unequal pitches and geometry outside the §16.5 comparison range are flagged for review.

Open calculator

Ground Rod Array

Dwight (1936), DOI 10.1109/T-AIEE.1936.5057209. The self-resistance of a rod of length L and radius a is ρ[ln(4L/a) − 1]/(2πL). The sleeve replaces a by its outer radius b and adds ρᵦ ln(b/a)/(2πL) for radial passage through the backfill.

Pair coupling is the average half-space potential for two uniformly leaking line electrodes. At separation s its coefficient is ρ[asinh(2L/s) − 2L/(√(s² + 4L²) + s)]/(2πL). Sum every pair twice, add n self-resistances, and divide by n² to estimate the bonded array under equal current sharing.

The hollow square distributes rods around a square lattice. The filled square starts at the perimeter, then fills interior lattice positions. Target search checks the first meeting count through 128 rods over the corresponding layout at each size.

Open calculator

Soil Resistivity Survey

IEEE Std 81-2012 §7.2.3, equations 2–3 and Annex A. Wenner uses 4πaR/[1 + 2a/√(a² + 4b²) − a/√(a² + b²)]. At b = 0 the result is 2πaR.

Schlumberger uses π(L − a/2)(L + a/2)R/a, where L is half the current-electrode span and a is the potential-electrode spacing. This geometry assumes shallow pins.

For the forward model, K = (ρ₂ − ρ₁)/(ρ₂ + ρ₁). Each image at depth 2nh contributes with weight Kⁿ. The series is evaluated for the two electrode distances and normalized by the homogeneous-soil geometric factor. The forward curve sweeps 0.1× to 10× the field spacing with a fixed array shape.

IEEE Std 81-2025 supersedes the 2012 guide. The published 2012 equations are the reference for this worksheet. Review the adopted edition for field procedures.

Open calculator

Ground Conductor Sizing

IEEE Std 80-2013 §11.3.1, equations 45–46 and Tables 1–2. IEEE Eq. 45 gives mm² from kA, seconds, TCAP in J/(cm³·°C), ρᵣ in μΩ·cm, and Celsius temperatures. The result is converted to kcmil using 1 kcmil = 0.506707479 mm².

The log term is ln[(K₀ + Tₘ)/(K₀ + Tₐ)]. The candidate utilization is required area / entered area. The thermal-energy utilization is its square. Standard sizes round up from the unrounded area.

The brazed and bolted connection caps are screening settings. Aluminum EC-0 and 5005-H19 resistivity and temperature coefficients come from NBS Handbook 109, Table 1. The aluminum heat capacity and lower melting limits are engineering approximations. Zinc-coated rod constants serve as a galvanized-steel proxy.

Open calculator

Lightning Rolling Sphere

IEC 62305-3:2024 and NFPA 780 rolling-sphere geometry. IEC LPL I–IV use 20, 30, 45 and 60 m. The NFPA radius preset is 150 ft (45.72 m). The NFPA geometry option keeps the IEC separation estimate separate and requires a user-supplied kᵢ.

The single-mast reach at object height hₓ equals √[h(2R − h)] − √[hₓ(2R − hₓ)] with h capped at R. Above the capped height there is no positive single-mast radius in this screen.

For equal masts spaced d apart, midpoint penetration is R − √(R² − d²/4), with d < 2R. Midpoint clearance must be positive. Contact with the rolling sphere leaves the object exposed. The separation estimate is kᵢk꜀l/kₘ.

Open calculator

Arc Flash Boundary

Lee (1982), DOI 10.1109/TIA.1982.4504068, and IEEE Std 1584-2002 Eq. 7 give the open-air screen E = 2.142 × 10⁶ VIbf t/D² in J/cm² for V in kV, Ibf in kA and D in mm.

The enclosed screen uses IEEE Std 1584-2002 equations 1–6 and Table 4. It estimates arcing current, then applies gap and grounding to normalized energy, with distance exponents 1.641 for LV panels/MCC, 1.473 for LV switchgear and 0.973 for MV switchgear. Clearing time is entered by the user. It can change sharply at reduced arcing current.

The boundary solves for 1.2 cal/cm² (5.0208 J/cm²) with clearing time and other inputs held constant. Clearing-time targets use the same model and geometry. Four reference energy ceilings (4, 8, 25 and 40 cal/cm²) help read the energy scale. NFPA 70E assigns PPE categories through the separate equipment-table method.

IEEE 1584-2018 supersedes the 2002 model and accounts for electrode orientation, enclosure dimensions, arcing-current variation and other effects absent from this worksheet. Even an estimate below 1.2 cal/cm² leaves electrical shock and other hazards to assess.

Open calculator

Earth-Fault Loop & CPC

IEC 60364-4-41 and IEC 60364-5-54. Zₛ = Zₑ + (R₁ + R₂) × temperature factor, with the floor current Iₑꜰ = U₀cₘᵢₙ/Zₛ and limit Zₛ,ₘₐₓ = U₀cₘᵢₙ/Iₐ. Resistances are added as a scalar screening approximation.

The B, C and D defaults use 5, 10 and 20 times In, respectively. For a gG fuse, enter the total-clearing current read from the manufacturer’s curve at the entered time. Use the manufacturer’s curve to determine disconnection time.

The adiabatic calculation is S = Iₑꜰ√t/k for the entered duty. Check the maximum relevant I²t and the applicable mechanical minimum separately. NEC Article 250 describes the effective ground-fault current path and has its own conductor sizing requirements.

Open calculator

Reference publications

  • IEEE Std 80-2013 (incorporates Cor 1-2015), Guide for Safety in AC Substation Grounding. IEEE Xplore 7109078.
  • IEEE Std 81-2012 §7.2.3 and Annex A. Current IEEE Std 81-2025 publication for field measurement guidance.
  • H. B. Dwight, Calculation of Resistances to Ground, 1936. DOI 10.1109/T-AIEE.1936.5057209.
  • U.S. National Bureau of Standards, Aluminum Wire Tables, Handbook 109, Table 1.
  • IEC 62305-3:2024 and NFPA 780, installation of lightning protection systems.
  • R. H. Lee, The Other Electrical Hazard: Electric Arc Blast Burns, 1982. DOI 10.1109/TIA.1982.4504068.
  • IEEE Std 1584-2002 §5 for the legacy screens. IEEE Std 1584-2018 for the current study model. NFPA 70E for workplace electrical safety and the two PPE selection methods.
  • IEC 60364-4-41:2005+A1:2017 and IEC 60364-5-54:2011+A1:2021. NFPA 70 (NEC), Article 250, for U.S. bonding and equipment grounding context.