GroundGridLab · Lee · legacy IEEE 1584
Resistance-grounded switchgear enclosure
A resistance-grounded LV enclosure is compared with a solidly grounded enclosure using the legacy normalization factor.
Above thermal boundary level. Preliminary estimate at the working position. PPE category requires the separate NFPA 70E table method.
- Incident energy
- 54.452 J/cm²
- Arc-flash boundary
- 3,077.1 mm
- Time to boundary level
- 0.027662 s
- Working distance
- 610 mm
Inputs
| Equipment model | LV switchgear · legacy 1584 |
|---|---|
| System line-to-line voltage | 0.6 kV |
| Three-phase bolted fault current | 22 kA |
| Electrode gap | 32 mm |
| System grounding | High-resistance / ungrounded |
| Arc clearing time | 0.3 s |
| Working distance from arc | 610 mm |
Derived values
| Energy in both systems | 13.014 cal/cm² / 54.452 J/cm² |
|---|---|
| Reference energy bracket | ≤ 25 cal/cm² |
| NFPA 70E PPE category | Separate equipment tables |
| Boundary reference | 5.021 J/cm² |
| Clearing ceiling at 8 cal/cm² | 0.18441 s |
| Clearing ceiling at 40 cal/cm² | 0.92207 s |
| Legacy arcing current | 15.35 kA |
| Distance exponent | 1.473 |
Preliminary screening only. Use an IEEE 1584-2018 study, actual protective-device coordination and a qualified NFPA 70E assessment for equipment labeling, PPE or energized-work decisions.