Cooling tower at four concentration cycles
An open evaporative tower rejects heat from a year-round industrial water loop.
Evaporative tower water balance
Makeup = E + D + B · B = max(0, E/(CoC − 1) − D)
- Approach
- 5K
- Range
- 7.5K
- Makeup flow
- 70.848L/min
- Annual cost
- 49.55KUSD/yr
- Within the displayed screening checks.
Inputs
Calculated results
- Wet-bulb approach
- 5 K
- Water cooling range
- 7.5 K
- Makeup flow
- 70.848 L/min
- Annual water cost
- 49,548 USD/yr
- Evaporation loss
- 53.136 L/min
- Drift loss
- 0.0984 L/min
- Blowdown flow
- 17.614 L/min
- Achievable concentration cycles
- 4
- Annual makeup volume
- 26,355 m³/yr
- Approximate heat rejection
- 2,565.6 kW
Worked solution
Preset calculation · Metric SI
- Find 7.5 K range from the water temperatures and 5 K approach from cold water and entering wet bulb.
- Calculate 53.136 L/min evaporation and 0.0984 L/min drift. The solids balance gives 17.614 L/min blowdown.
- Add the three losses to get 70.848 L/min makeup. With the given hours and tariff, the annual cost is 49,548 USD/yr.
Check that evaporation, drift and blowdown add to makeup. The five-kelvin approach is separate from the cooling range.
Calculation basis
Range is hot minus cold water. Approach is cold water minus entering wet bulb. The approximate rejection load uses 998 kg/m³ and 4.18 kJ/kg·K for water.
The default evaporation factor is 0.08% of circulation per °F of range. Drift is an entered fraction of circulation. Cycles use a steady-state dissolved-solids balance with zero mineral loss through evaporation.
If drift meets or exceeds the permissible concentrated water loss, blowdown is zero and attainable cycles can be below the target. Annual cost multiplies makeup flow by entered run hours and the water price.
Methodology and references