Calculation basis
Each worksheet evaluates steady-state inputs in SI and converts the display to the selected unit system. Temperatures and temperature differences use separate conversions. US liquid volumes use US gallons.
The models support preliminary thermal sizing and hydraulic screening. Confirm fluid properties, material and corrosion allowances, fabrication limits, and supplier performance for the operating case.
Example presets show initial inputs and their worked solution. Edits change the active result. Any shared link includes inputs in SI and the selected display system.
LMTD & exchanger area
Q = U × A × Fₜ × ΔTₗₘ
Enter four terminal temperatures, a target duty, and a service U. Required surface meets the target duty at the specified conditions. Available duty rates the entered surface at those same conditions.
The two terminal differences define ΔTₗₘ. Equal terminal differences give that exact difference. Parallel and counterflow use Fₜ = 1 with their own terminal pairing.
For ideal 1–2 and 2–4 shell arrangements, Fₜ corrects the counterflow mean using Bowman–Mueller–Nagle P and R. Fₜ below 0.75 warrants a layout review. Terminal temperatures must also lie inside the feasible Fₜ domain.
- Bowman, Mueller & Nagle (1940), Mean Temperature Difference in Design
- Fakheri (2003), LMTD correction factor for shell-and-tube exchangers
Effectiveness–NTU rating
NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)
Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.
Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.
Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.
- Kays & London (1984), Compact Heat Exchangers, third edition
- ASHRAE Fundamentals, Chapter 4, effectiveness–NTU equations
- Triboix (2009), exact and approximate solutions for unmixed crossflow
Overall U & fouling
U = 1 / ΣR · Rwall,tube = rₒ ln(rₒ / rᵢ) / k
For a tube, results refer to outside surface area. Multiply inside film and inside fouling by rₒ/rᵢ. The cylindrical wall uses rₒ ln(rₒ/rᵢ)/k.
For a flat plate, both sides have the same area and wall resistance is thickness divided by conductivity. Clean U omits both fouling allowances.
Enter service-specific fouling factors on their local surface basis, using the project or TEMA allowance. The 80% cleanliness check is a worksheet screening value.
- ASHRAE Fundamentals, Chapter 4, overall heat transfer coefficient
- TEMA, standards for tubular exchanger design and fouling allowances
Tube count & pressure drop
ΔP = [f × (L/Dᵢ) × nₚ + 4(nₚ − 1)] × ρv²/2
Required outside area divided by πDₒL gives the raw tube count. Round up to fill complete passes. Bundle capacity counts centers on the selected pitch lattice inside a circular limit after bundle clearance.
The bundle screen uses a centered lattice and omits pass-partition lanes, tie rods, and detailed tubesheet constraints. Confirm actual tube count with a layout drawing.
Straight loss uses Darcy–Weisbach with 64/Re for laminar flow and Haaland for turbulent flow. Add K = 4 per return pass. The default 0.9–2.4 m/s screening band is for initial liquid-service review.
Open calculatorKern shell-side rating
Aₛ = DₛB(p − Dₒ)/p · Nu = 0.36 Re⁰·⁵⁵ Pr¹ᐟ³ (μ/μwall)⁰·¹⁴
Kern crossflow area uses the notional tube row at the shell equator. Equivalent diameter comes from the open area and wetted perimeter of a square or triangular pitch cell.
The 25% nominal baffle-cut correlation estimates shell-side hₒ and pressure drop. The entered cut changes the gross segment window and diagram. Leakage, bypass, window obstructions, and nozzle losses require a more detailed method.
The spacing screen runs from the larger of 0.2Dₛ and 50 mm to Dₛ. Maximum unsupported length and vibration depend on the actual tube material and layout.
Open calculatorPlate count & channel shear
Nactive ≥ Q / (U × ΔT × Aplate) · τw = fᴅρv²/8
Use active plate width and length, excluding the port area. Corrugation enlargement multiplies projected plate area. The pack includes two non-transfer end plates and rounds up to equal channels per side and pass.
The hydraulics are for the entered stream. Hydraulic diameter is 2b/φ. A Martin chevron friction factor estimates core pressure drop and average wall shear. Port and multi-pass turning losses are omitted.
Wall shear over 50 Pa is an illustrative antifouling screen. Use supplier predictions and fluid-specific deposition data for final selection.
- Martin (1996), performance of chevron-type plate heat exchangers
- Walraven et al. (2014), Appendix A, plate pressure drop and Fanning factor
Fin efficiency & fan power
ηₒ = 1 − (Af/At)(1 − ηf) · Pshaft = V̇air × ΔPair / ηfan
Annular discs use the Schmidt corrected-radius approximation. Rectangular plates use a square outer boundary and a straight-fin efficiency approximation with a corrected tip length.
Total outside area includes both fin faces, exposed fin edges, and the tube area left between fins. ηₒ weights the fin and bare areas at a common airside film coefficient.
Enter an allowable air temperature rise to size the airflow, or use known airflow to predict the rise. Shaft power uses the total air-path pressure drop and fan efficiency. Motor input would also require motor and drive efficiencies.
- ASHRAE Fundamentals, Chapter 4, fin efficiency and extended surfaces
- Bošnjaković et al. (2019), annular fin efficiency and corrected tip radius
Cooling tower makeup
Makeup = E + D + B · B = max(0, E/(CoC − 1) − D)
Range is hot minus cold water. Approach is cold water minus entering wet bulb. The approximate rejection load uses 998 kg/m³ and 4.18 kJ/kg·K for water.
The default evaporation factor is 0.08% of circulation per °F of range. Drift is an entered fraction of circulation. Cycles use a steady-state dissolved-solids balance with zero mineral loss through evaporation.
If drift meets or exceeds the permissible concentrated water loss, blowdown is zero and attainable cycles can be below the target. Annual cost multiplies makeup flow by entered run hours and the water price.
Open calculator