Carbon Dioxide Gas Metering
Estimate a gas-phase CO₂ branch valve at moderate pressure using known Cv.
Inputs
View results ↓Results
Edit inputs ↑- Valve flow coefficient
- 1.2 Cv
- Metric flow coefficient
- 1.038 Kv
- Standard gas flow
- 24.862 SCFM
- ISA valve flow regime
- Subsonic
- Estimated sonic conductance
- 3.1808 L/(s·bar)
- Absolute outlet / inlet ratio
- 0.59433
- ISA outlet / inlet at choke
- 0.50281
- 0.53 air-orifice screen
- Subsonic
- Gas expansion factor Y
- 0.72802
- Gas specific gravity
- 1.519
- Gas heat capacity ratio
- 1.289
Formula and assumptions
Find the ISA choking point
x = 1 − P₂/P₁ · xcrit = (γ/1.4)xT · xs = min(x, xcrit) · Y = 1 − xs/(3xcrit)
Use absolute pressures. The air-orifice screen is P₂/P₁ ≤ 0.53. With air and the default xT of 0.47 it matches the rounded valve threshold. Use the OEM factor for the actual valve opening or installed xTP with the matching piping factor Fp.
Solve for Cv or standard flow
qscfh = 7,320 × Fp × Cv × P₁ × Y × √(xs/(M × T₁))
The ANSI/ISA-75.01.01 and IEC 60534-2-1 style equation shown uses P₁ in psia, gas molecular mass M in lb/lb-mol, and T₁ in °R. M = 28.96546 × gas specific gravity. This ideal-gas approximation sets Z = 1. Kv is approximately 0.865 × Cv.
Compare equivalent sonic conductance
Ceq = predicted choked reference flow in L/s ÷ upstream bar(a)
The estimate uses dry gas at 20 °C and 1 bar for the reference volume and 20 °C at the inlet. ISO 6358-1 catalogs flow characteristics from testing. Use measured C and critical back-pressure ratio for OEM pneumatic component selection.
Flow labels use dry gas at 101.325 kPa, with 60 °F for SCFM and 0 °C for normal metric flow. See all unit conventions.
Worked examples
-
Air Control Valve Near the Choke Point
Find the Cv for 125 SCFM through an air valve with a modest downstream pressure drop.
-
Choked Air Exhaust Valve
Predict the available airflow through a known Cv venting a pressurized air manifold.
-
Nitrogen Inerting Valve
Size a control valve for industrial nitrogen purge flow through a pressurized branch.
-
Carbon Dioxide Gas Metering
Estimate a gas-phase CO₂ branch valve at moderate pressure using known Cv.
-
Argon Control Valve in Metric Units
Size a valve for 1,800 NL/min of argon using a lower installed piping factor.
-
Low Differential Across a Valve
Determine available flow when an installed valve sees only a 1.5 psi pressure drop.