Nitrogen Inerting Valve

Size a control valve for industrial nitrogen purge flow through a pressurized branch.

Inputs

View results ↓
Pressure and gas
psig
psig
°F
Valve and sizing target
SCFM
Use OEM xT or installed xTP at the intended opening.

Results

Edit inputs ↑
Valve flow versus pressure ratio VALVE CV 1.113 CvVALVE KV 0.963 KvGAS FLOW 55 SCFMISA REGIME Subsonic NORMALIZED FLOW ISA CHOKE OPERATING POINT ABSOLUTE PRESSURE RATIO 0.5486 0 0.53 AIR SCREEN 1.0
Valve flow versus pressure ratio
Valve flow coefficient
1.1133 Cv
Metric flow coefficient
0.96304 Kv
Standard gas flow
55 SCFM
ISA valve flow regime
Subsonic
Estimated sonic conductance
3.9944 L/(s·bar)
Absolute outlet / inlet ratio
0.54863
ISA outlet / inlet at choke
0.42
0.53 air-orifice screen
Subsonic
Gas expansion factor Y
0.74059
Gas specific gravity
0.9672
Gas heat capacity ratio
1.4

Formula and assumptions

Find the ISA choking point

x = 1 − P₂/P₁ · xcrit = (γ/1.4)xT · xs = min(x, xcrit) · Y = 1 − xs/(3xcrit)

Use absolute pressures. The air-orifice screen is P₂/P₁ ≤ 0.53. With air and the default xT of 0.47 it matches the rounded valve threshold. Use the OEM factor for the actual valve opening or installed xTP with the matching piping factor Fp.

Solve for Cv or standard flow

qscfh = 7,320 × Fp × Cv × P₁ × Y × √(xs/(M × T₁))

The ANSI/ISA-75.01.01 and IEC 60534-2-1 style equation shown uses P₁ in psia, gas molecular mass M in lb/lb-mol, and T₁ in °R. M = 28.96546 × gas specific gravity. This ideal-gas approximation sets Z = 1. Kv is approximately 0.865 × Cv.

Compare equivalent sonic conductance

Ceq = predicted choked reference flow in L/s ÷ upstream bar(a)

The estimate uses dry gas at 20 °C and 1 bar for the reference volume and 20 °C at the inlet. ISO 6358-1 catalogs flow characteristics from testing. Use measured C and critical back-pressure ratio for OEM pneumatic component selection.

Flow labels use dry gas at 101.325 kPa, with 60 °F for SCFM and 0 °C for normal metric flow. See all unit conventions.