Worked calculation
Estimate R and X per conductor, multiply the projected impedance by 375 ft converted to km, then apply √3·190. Check XLPE cable withstand at the 0.20 s clearing time.
- Longitudinal voltage drop
- 8.77 V
- Longitudinal drop percent
- 1.827%
- Withstand across parallel sets
- 34.28 kA
Values in this solution use the original example inputs.
Formulas & assumptions
Balanced three-phase lagging load. The effective R/X model omits installation-specific spacing and heating. The 0.01–5 s adiabatic screen requires conductor and termination checks. For current-limiting devices, use published let-through I²t and verify coordination.
Engineering references