400 mm² PVC aluminum cable

A 400 V, 50 Hz feeder uses 400 mm² aluminum with PVC insulation and a one-way run of 95 m.

Inputs

Conductor & raceway
Steady load
Cable thermal duty
Use 0 to show withstand only.

Feeder impedance and cable withstand

50 Hz · MetricEdit inputs
Feeder impedance and cable withstand at 50 Hz AC DROP6.2VDROP PCT1.549%LOAD VOLTS393.8VTHERMAL LIMIT38.47kAThree-phase feederSourceLoadL1L2L3One-way 95 m1 × setsR + jX per phase6.2 V dropAdiabatic clearing curveWithstand (kA)0.01 s5 sDrop budget1.55% drop3% budget

Detailed results
Longitudinal voltage drop
6.2 V
Longitudinal drop percent
1.549%
Phasor receiving line voltage
393.8 V
Phasor magnitude voltage drop
6.2 V
AC resistance per conductor
0.0983 Ω/km
Reactance per conductor
0.0757 Ω/km
Equivalent one-way resistance
0.00934 Ω
Equivalent one-way reactance
0.0072 Ω
Conductor cross-section
400 mm²
Adiabatic conductor coefficient
68 A√s/mm²
Withstand per conductor
38.47 kA
Withstand across parallel sets
38.47 kA
Allowable I²t per conductor
739,840,000 A²s
Modeled fault I²t per conductor
512,000,000 A²s
Adiabatic limit used
69.2%

Worked calculation

For PVC above 300 mm² use the aluminum coefficient 68 A√s/mm². Divide 68·400 A√s by √0.5 s for the per-conductor current limit.

Adiabatic conductor coefficient
68 A√s/mm²
Withstand across parallel sets
38.47 kA
Allowable I²t per conductor
739,840,000 A²s

Values in this solution use the original example inputs.

Formulas & assumptions

Three-phase longitudinal drop

ΔV = √3 · I · L · (R · cos φ + X · sin φ) / n

Use a one-way length with matching R/X units and divide by the number of identical parallel sets. The longitudinal expression is the common steady-load approximation. The magnitude result retains the quadrature term and solves for receiving voltage.

Resistance and reactance

R₇₅ ≈ 1000 · ρ₇₅ · F_AC / A, X ≈ 2πf · 0.0002 · ln(2.6/0.7788) · F_raceway

Estimated Ω/km uses round conductors, ρ₇₅ of 0.02097 (Cu) or 0.0347 (Al) Ω·mm²/m, F_AC = 1 + min(0.18, A/3000) · g, with g = 1.5 for steel or 1 for PVC. The reactance multiplier is 1.2 for steel and 1 for PVC. Enter manufacturer AC R/X at operating temperature and frequency when available.

Short-circuit thermal withstand

I²t ≤ (k · A)², I_max = k · A / √t

A is the area of one conductor in mm². k depends on insulation, metal and the permitted temperature rise. Total withstand assumes equal current in all sets. The PVC coefficient changes above 300 mm².

Balanced three-phase lagging load. The effective R/X model omits installation-specific spacing and heating. The 0.01–5 s adiabatic screen requires conductor and termination checks. For current-limiting devices, use published let-through I²t and verify coordination.