Feeder with catalog R and X

A 480 V switchboard feeder uses a 250 m run. Its manufacturer gives 0.190 Ω/km AC resistance and 0.082 Ω/km reactance.

Inputs

Conductor & raceway
Enter per-conductor catalog reactance at the selected frequency.
Steady load
Cable thermal duty
Use 0 to show withstand only.

Feeder impedance and cable withstand

60 Hz · MetricEdit inputs
Feeder impedance and cable withstand at 60 Hz AC DROP18.71VDROP PCT3.897%LOAD VOLTS461.29VTHERMAL LIMIT38.37kAThree-phase feederSourceLoadL1L2L3One-way 250 m1 × setsR + jX per phase18.71 V dropAdiabatic clearing curveWithstand (kA)0.01 s5 sDrop budget3.9% drop3% budget
  • Calculated voltage drop exceeds the entered planning budget.

Detailed results
Longitudinal voltage drop
18.71 V
Longitudinal drop percent
3.897%
Phasor receiving line voltage
461.29 V
Phasor magnitude voltage drop
18.71 V
AC resistance per conductor
0.19 Ω/km
Reactance per conductor
0.082 Ω/km
Equivalent one-way resistance
0.0475 Ω
Equivalent one-way reactance
0.0205 Ω
Conductor cross-section
120 mm²
Adiabatic conductor coefficient
143 A√s/mm²
Withstand per conductor
38.37 kA
Withstand across parallel sets
38.37 kA
Allowable I²t per conductor
294,465,600 A²s
Modeled fault I²t per conductor
51,200,000 A²s
Adiabatic limit used
17.39%

Worked calculation

Use √3·210·0.25·[0.190·0.87 + 0.082·√(1−0.87²)] for longitudinal drop. The full phasor result also includes the quadrature drop.

Longitudinal voltage drop
18.71 V
Phasor magnitude voltage drop
18.71 V
Phasor receiving line voltage
461.29 V

Values in this solution use the original example inputs.

Formulas & assumptions

Three-phase longitudinal drop

ΔV = √3 · I · L · (R · cos φ + X · sin φ) / n

Use a one-way length with matching R/X units and divide by the number of identical parallel sets. The longitudinal expression is the common steady-load approximation. The magnitude result retains the quadrature term and solves for receiving voltage.

Resistance and reactance

R₇₅ ≈ 1000 · ρ₇₅ · F_AC / A, X ≈ 2πf · 0.0002 · ln(2.6/0.7788) · F_raceway

Estimated Ω/km uses round conductors, ρ₇₅ of 0.02097 (Cu) or 0.0347 (Al) Ω·mm²/m, F_AC = 1 + min(0.18, A/3000) · g, with g = 1.5 for steel or 1 for PVC. The reactance multiplier is 1.2 for steel and 1 for PVC. Enter manufacturer AC R/X at operating temperature and frequency when available.

Short-circuit thermal withstand

I²t ≤ (k · A)², I_max = k · A / √t

A is the area of one conductor in mm². k depends on insulation, metal and the permitted temperature rise. Total withstand assumes equal current in all sets. The PVC coefficient changes above 300 mm².

Balanced three-phase lagging load. The effective R/X model omits installation-specific spacing and heating. The 0.01–5 s adiabatic screen requires conductor and termination checks. For current-limiting devices, use published let-through I²t and verify coordination.