Linear load with no harmonics

A 165 A industrial load operates with 0.86 displacement PF and no reported harmonic current.

Inputs

Measurement & connection
Use manufacturer loss data for the limiting winding. Enter 0 to omit the derating screen.
Harmonic magnitudes

Harmonic spectrum and neutral stacking

60 Hz · US customaryEdit inputs
Harmonic spectrum and neutral stacking at 60 Hz THD-I0%LINE RMS165ATRIPLEN N0AK-FACTOR1Phase current spectrum165 A scale60 Hz baseh1h3h5h7h9h11h13Triplen neutral pathL1L2L3NNeutral RMS0 ATriplen orders3 · 9True power factor86%1.0 PF

Detailed results
Current total harmonic distortion
0%
Total RMS phase current
165 A
Harmonic RMS excluding fundamental
0 A
Distortion factor
1
True power factor
0.86
Balanced triplen neutral RMS
0 A
Neutral relative to phase RMS
0%
RMS-normalized K-factor
1
Winding-loss current limit / rated current
Unavailable

Spectrum by harmonic

OrderFrequencyRMS current% of I₁
h160 Hz165 A100%
h3180 Hz0 A0%
h5300 Hz0 A0%
h7420 Hz0 A0%
h9540 Hz0 A0%
h11660 Hz0 A0%
h13780 Hz0 A0%

Worked calculation

With all higher orders set to zero, true RMS equals 165 A, the distortion factor is one and the K-factor equals 1².

Total RMS phase current
165 A
True power factor
0.86
RMS-normalized K-factor
1

Values in this solution use the original example inputs.

Formulas & assumptions

THD-I and true RMS

THD = √Σ(I_h², h > 1) / I₁, I_RMS = √ΣI_h²

Percent-mode entries use the fundamental as their reference. The spectrum covers odd orders through 13. The frequency of a component is its order times 50 Hz or 60 Hz.

True power factor

PF_true = PF_displacement / √(1 + THD²)

Use THD as a decimal. This relationship assumes sinusoidal voltage, so real power comes from the fundamental voltage and current.

Triplen neutral and thermal weighting

I_N = 3 · √(I₃² + I₉²), K = Σ[(I_h/I_RMS)² · h²]

Third and ninth harmonics add arithmetically across balanced four-wire Wye phases at each order. Different orders combine by RMS. The K-factor uses total RMS as the base and the harmonic winding eddy-current weighting associated with IEEE C57.110.

Winding-loss current limit

I_max/I_rated ≈ √[(1 + e)/(1 + K · e)]

e is rated winding eddy-current loss divided by rated winding DC I²R loss. This holds the winding loss constant for the entered spectrum and excludes other stray losses and cooling constraints.

Equal phase spectra with balanced sequence and sinusoidal voltage. The displayed THD-I describes the entered current spectrum. IEEE 519 limits are assessed at the point of common coupling with the applicable quantities, including TDD. Transformer thermal loading also depends on construction and rated current.

Engineering references