THD-I and true RMS
THD = √Σ(I_h², h > 1) / I₁, I_RMS = √ΣI_h²
Percent-mode entries use the fundamental as their reference. The spectrum covers odd orders through 13. The frequency of a component is its order times 50 Hz or 60 Hz.
A 50 Hz analyzer reports 15% third, 30% fifth, 18% seventh, 2% ninth, 7% eleventh and 5% thirteenth at 200 A fundamental.
| Order | Frequency | RMS current | % of I₁ |
|---|---|---|---|
| h1 | 50 Hz | 200 A | 100% |
| h3 | 150 Hz | 30 A | 15% |
| h5 | 250 Hz | 60 A | 30% |
| h7 | 350 Hz | 36 A | 18% |
| h9 | 450 Hz | 4 A | 2% |
| h11 | 550 Hz | 14 A | 7% |
| h13 | 650 Hz | 10 A | 5% |
Convert 30% fifth to 60 A and 18% seventh to 36 A. The fifth order occurs at 250 Hz. THD-I is the RMS sum of the percentages.
Values in this solution use the original example inputs.
THD = √Σ(I_h², h > 1) / I₁, I_RMS = √ΣI_h²
Percent-mode entries use the fundamental as their reference. The spectrum covers odd orders through 13. The frequency of a component is its order times 50 Hz or 60 Hz.
PF_true = PF_displacement / √(1 + THD²)
Use THD as a decimal. This relationship assumes sinusoidal voltage, so real power comes from the fundamental voltage and current.
I_N = 3 · √(I₃² + I₉²), K = Σ[(I_h/I_RMS)² · h²]
Third and ninth harmonics add arithmetically across balanced four-wire Wye phases at each order. Different orders combine by RMS. The K-factor uses total RMS as the base and the harmonic winding eddy-current weighting associated with IEEE C57.110.
I_max/I_rated ≈ √[(1 + e)/(1 + K · e)]
e is rated winding eddy-current loss divided by rated winding DC I²R loss. This holds the winding loss constant for the entered spectrum and excludes other stray losses and cooling constraints.
Equal phase spectra with balanced sequence and sinusoidal voltage. The displayed THD-I describes the entered current spectrum. IEEE 519 limits are assessed at the point of common coupling with the applicable quantities, including TDD. Transformer thermal loading also depends on construction and rated current.