Three-wire rectifier spectrum

A balanced three-wire industrial rectifier input shows strong 5th and 7th harmonic content, with no neutral conductor.

Inputs

Measurement & connection
Use manufacturer loss data for the limiting winding. Enter 0 to omit the derating screen.
Harmonic magnitudes

Harmonic spectrum and neutral stacking

60 Hz · US customaryEdit inputs
Harmonic spectrum and neutral stacking at 60 Hz THD-I39.1%LINE RMS161.06ATRIPLEN N—K-FACTOR6.252Phase current spectrum150 A scale60 Hz baseh1h3h5h7h9h11h13Triplen neutral pathL1L2L3Three-wire connectionTriplen orders3 · 9True power factor85.68%1.0 PF

Detailed results
Current total harmonic distortion
39.1%
Total RMS phase current
161.06 A
Harmonic RMS excluding fundamental
58.64 A
Distortion factor
0.93135
True power factor
0.85685
Balanced triplen neutral RMS
Unavailable
Neutral relative to phase RMS
Unavailable
RMS-normalized K-factor
6.252
Winding-loss current limit / rated current
Unavailable

Spectrum by harmonic

OrderFrequencyRMS current% of I₁
h160 Hz150 A100%
h3180 Hz0 A0%
h5300 Hz47 A31.33%
h7420 Hz31 A20.67%
h9540 Hz0 A0%
h11660 Hz13 A8.67%
h13780 Hz10 A6.67%

Worked calculation

Use 47 A fifth and 31 A seventh in THD and K-factor. The 3-wire model leaves neutral current unavailable.

Current total harmonic distortion
39.1%
Balanced triplen neutral RMS
Unavailable
RMS-normalized K-factor
6.252

Values in this solution use the original example inputs.

Formulas & assumptions

THD-I and true RMS

THD = √Σ(I_h², h > 1) / I₁, I_RMS = √ΣI_h²

Percent-mode entries use the fundamental as their reference. The spectrum covers odd orders through 13. The frequency of a component is its order times 50 Hz or 60 Hz.

True power factor

PF_true = PF_displacement / √(1 + THD²)

Use THD as a decimal. This relationship assumes sinusoidal voltage, so real power comes from the fundamental voltage and current.

Triplen neutral and thermal weighting

I_N = 3 · √(I₃² + I₉²), K = Σ[(I_h/I_RMS)² · h²]

Third and ninth harmonics add arithmetically across balanced four-wire Wye phases at each order. Different orders combine by RMS. The K-factor uses total RMS as the base and the harmonic winding eddy-current weighting associated with IEEE C57.110.

Winding-loss current limit

I_max/I_rated ≈ √[(1 + e)/(1 + K · e)]

e is rated winding eddy-current loss divided by rated winding DC I²R loss. This holds the winding loss constant for the entered spectrum and excludes other stray losses and cooling constraints.

Equal phase spectra with balanced sequence and sinusoidal voltage. The displayed THD-I describes the entered current spectrum. IEEE 519 limits are assessed at the point of common coupling with the applicable quantities, including TDD. Transformer thermal loading also depends on construction and rated current.