Induction motor starting & VFD savings calculator

Estimate motor full-load and locked-rotor amps, compare starter voltage dip, and calculate centrifugal pump or fan energy savings using the cube law.

Inputs

Motor nameplate
Use 0 for the code range midpoint, or the lower bound for open-ended Code V.
Starter & bus
Centrifugal duty

Starting voltage dip and cubic power

60 Hz · US customaryEdit inputs
Starting voltage dip and cubic power at 60 Hz FULL LOAD107.21ALOCKED ROTOR715.67AVOLTAGE DIP4.36%ENERGY SAVED154.9KkWhBus voltage during startingNominal bus480 VEstimated during start459.06 VStarting demand595 kVACentrifugal affinity curve100% power0% speed100% speedVoltage dip4.36%8% budget

Detailed results
Mechanical shaft rating
74.57 kW
Baseline electrical power
79.33 kW
Estimated full-load line current
107.21 A
Inrush ratio used
5.95 kVA/hp
Nominal DOL locked-rotor current
715.67 A
Code band lower current
673.58 A
Code band upper current (exclusive)
757.77 A
Selected starting current
715.67 A
Starting apparent power
595 kVA
Bus short-circuit capacity
13.04 MVA
Bus voltage dip
4.36%
Reduced-speed electrical power
40.62 kW
Baseline energy per year
317,319.09 kWh
Reduced-speed energy per year
162,467.38 kWh
Annual energy savings
154,851.72 kWh
Annual energy cost savings
18,582.21 USD/yr

Formulas & assumptions

Nameplate and inrush

I_FLA = 1000 · kW_shaft / (√3 · V_LL · η · PF), SKVA_DOL = hp · (kVA/hp)

Use operating-frequency nameplate data. Bounded NEMA codes use the midpoint of their interval. Code V has no upper bound. The measured inrush ratio can supersede the estimate.

Starter and source dip

Dip (%) = 100 · SKVA / (SKVA + 1000 · MVA_sc)

DOL uses the full code estimate. Wye-Delta uses one-third of DOL line current for a Delta-running motor. Soft starter and VFD inputs set modeled current in multiples of FLA. For the transformer-only source, MVA_sc = transformer kVA / (1000 · %Z/100).

Centrifugal affinity law

P₂ = P₁ · (N₂/N₁)³, ΔkWh = (P₁ − P₂) · annual hours

Assumes the same operating hours, friction-dominated duty and unchanged efficiency, with drive losses excluded. Run this part for variable-torque pumps and fans with minimal static head.

Use actual nameplate current and starting curves for equipment sizing. The impedance-divider dip is a screening estimate without cable impedance, source X/R or Wye-Delta transition transients.